ET-2200 Series Ethernet I/O Modules
3. Click the "Pair" tab to display the I/O Pair-connection Settings page.
5.1.1

Pull Mode

1. In the Pair-Connection Setting section, choose PULL and check the box in the Enable Mode
field to enable this mode.
2. In the Remote IP... : Port fields, enter the IP address and TCP Port of the remote ET-2260#2
module.
3. In the IO Count field, enter the mapped quantity for DI and DO.
For example, the PULL Mode (Remote DI to Local DO) configuration:
Enter "2" in the "IO Count" field and "0" in both the Local/Remote IO Address fields. This
means
DI0
and DI1 of ET-2260#2 module correspond to
4. In the Local IO Address field, select "0x: Coil Output..." and enter the starting DO address.
In the Remote IO Address field, select "1x: Discrete Input.." and enter the starting DI address.
5. Choose the Modbus protocol (e.g., TCPv4) from the Network Protocol drop-down menu.
6. Click the "Submit..." button to complete the configuration.
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
DO0
and DO1 of ET-2260#1 module.