ET-2200 Series Ethernet I/O Modules
Step 4-2: Configure the Pair-Connection for the ET-2260#2 (Push Mode)
1. Click the Pair tab to display the configuration page.
2. In the Pair-Connection Setting section, choose PUSH and check the box in the Enable Mode
field to enable this mode.
3. In the Remote IP... : Port fields, enter the IP address and the TCP Port of the remote ET-2260#1
module
4. In the IO Count field, enter the mapped quantity for DI and DO.
For example, the PUSH Mode (Local DI to Remote DO) configuration:
Enter "1" in the IO Count field and "0" in both the Local/Remote IO Address fields.
This means
DI0
5. In the Local IO Address field, select "1x: Discrete Input.." and enter the starting DI address.
In the Remote IO Address field, select "0x: Coil Output..." and enter the starting DO address.
6. Choose the Modbus protocol (e.g., TCPv4) from the Network Protocol drop-down menu.
7. Click the "Submit..." button to complete the configuration.
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
of ET-2260#2 module correspond to
DO0
of ET-2260#1 module.