Step4: In the Set Output field, enter a maximum voltage (or current) value in Engineering format
and click the Set button. Also, check the output value using a digital multimeter. Click the
Calibration Apply button to perform the calibration.
Type
Full-scale Range
Note:
The output voltage (or current) must be very close to the full-scale value.
For example, when calibrating a 10 V output, the output should be between 9900 and
9990. If the digital multimeter displays "10.0315V" while the output is set to 9900, the user
can lower the output to the value (9960) that is closest to the 10 V shown on the digital
multimeter. Afterward, click the Calibration Apply button.
Step5: After completing the calibration, click the "Run Mode" button to back to the Run mode.
Note:
The user can click the Restore Defaults button on the Network page to restore the settings
to the factory defaults.
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
+10V
+5V
9900 ~ 9990
4900 ~ 4990
1
.
4mA
20mA
6900 ~ 7100
18800 ~ 18900
3
.
2
.
-56 -