ET-2200 Series Ethernet I/O Modules
Host
Refer to Chapter 5 - I/O Pair Connection Application for detailed configuration
1. Click Enable Mode and choose the PULL mode (Remote DI to Local DO) to enable this function
(#01 ~ #08).
2. In the Remote IP... : Port field, enter the IP address and TCP port (502) of remote modules
(Slave #1-8). In the IO Count field, enter the number of mapped DI (e.g., 16).
In the Local IO Address field, select "0x: Coil Output..." and enter the starting address of the
shared memory.
In the Remote IO Address field, select "1x: Discrete Input..." and enter the starting DI address.
3. In Shared Memory, the host computer has the option to use either Bit or Register addresses to
poll ET-2200, and both approaches can read the same data. Accessing a Register is equivalent
to accessing 16 bits.
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
ET-2200 +
Concentrator
10.0.8.200
Remote IP
IP
(Slave #1-8 )
10.0.8.10
10.0.8.11
10.0.8.12
10.0.8.13
10.0.8.14
10.0.8.15
10.0.8.16
10.0.8.17
IO Address
(Shared Memory)
3000...3015
3016...3031
3032...3047
3048...3063
3064...3079
3080...3095
3096...3111
3112...3127
-130 -