ET-2200 Series Ethernet I/O Modules
Step2: In the Calibration section of the I/O Settings page, click the Calibration Mode button to get
into the calibration mode.
Step3: Choose a channel for calibration and link the module to the digital multimeter.
Voltage Calibration:
The module and digital multimeter are linked in series.
Current Calibration:
The module and digital multimeter are linked in parallel.
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
Run / Calibration
Digital
Multimeter
V
AGND
Digital
Multimeter
A
Calibration / Run
Vinx
Iinx
AGND
Mode
-55 -