ET-2200 Series Ethernet I/O Modules
5.5.1
Address Mapping for Shared Memory
Note:
All DI, DO, AI, and AO signals shared a single memory space. The storage address starts at 3000.
Writing 16 bits of DI/DO data to addresses
register to the address 3000.
Writing 16 bits of DI/DO data to addresses
register to the address 3001.
The correspondence of addresses is as follows, using the division to take the quotient and remove
the remainder.
AIO_Address = (DIO_Address – 3000) / 16 + 3000
Copyright © 2023 ICP DAS CO., Ltd. All Rights Reserved.
3000
–
3015
is equivalent to writing one 16-bit AI/AO
3016
–
3031
is equivalent to writing one 16-bit AI/AO
-128 -