10 | Specifications

10
Specifications
10.1

Reactive power control

Reactive power can be used in electrical energy supply networks to bolster the level of voltage. As such, feed-in inverters
can contribute to statistical voltage stability. Reactive power brings about a voltage drop at the inductive and capacitive
components of the equipment which can either bolster or reduce the level of voltage. If the generating plant draws induc-
tive reactive power while active power is being fed in, part of the voltage swing caused by the active power feed can be
compensated for by the supply of reactive power.
This reactive power mode and the respective control process are specified by the grid operator. If no control process has
been specified, then the plant should be operated using a reactive power specification of 0%.
10.1.1 Operating power range depending on grid voltage
The device can be operated within the respective fixed voltage range provided. The maximum apparent power is stated in
the following table. In the event of undervoltage determined by the maximum continuous current subject to the grid volt-
age.
The following figures show the reactive power operating range subject to active power and the apparent power operating
range subject to the grid voltage for various devices.
Maximum
bp 87.0
bp 92.0
apparent
TL3
TL3
power
Voltage
Voltage
[p.u.]
U
: 380V
U
: 400V
N
N
1,10
-
-
1,00
≥ 380
≥ 400
0,95
361
380
0,90
342
360
0,85
323
340
Tab. 8: Maximum continuous apparent power depending on grid voltage
P [p.u.]
1,2
1
0,8
0,6
0,4
0,2
0
1
0,6
0,0
underexcited
Fig. 65: P-Q operating range for bp 87.0 TL3 (Q
P [p.u.]
1,2
1
0,8
0,6
0,4
0,2
0
1
0,6
0,0
underexcited
Fig. 67: P-Q operating range for bp 92.0 TL3 (Q
Page 78
bp 105
bp 125
bp 137
TL3
TL3
TL3
Voltage
Voltage
Voltage
U
: 400V
U
: 600V
U
: 600V
N
N
N
-
≥ 600
-
≥ 380
545
≥ 600
361
520
570
342
492
540
323
464
510
U
380V
N
above U
N
at 0,95 U
N
at 0,9 U
N
at 0,85 U
N
0,6
1
Q [P.u]
overexcited
=S
)
max
max
U
400V
N
above U
N
at 0,95 U
N
at 0,9 U
N
at 0,85 U
N
0,6
1
Q [P.u]
overexcited
=S
)
max
max
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Manual
bp 150
bp 155
TL3
TL3
Voltage
Voltage
U
: 660V
U
: 590V
N
N
-
-
≥ 660
≥ 590
627
560
590
530
561
502
S [p.u. S
]
nom
1,2
1
0,8
0,6
Nominal
Disconnection
OVRT
capability
0,4
0,2
0
580
540
500
460
420
Fig. 66: Apparent power subject to the grid voltage for bp
87.0 TL3
S [p.u. S
]
nom
1,2
1
0,8
0,6
Nominal
Disconnection
OVRT
capability
0,4
0,2
0
580
540
500
460
420
Fig. 68: Apparent power subject to the grid voltage for bp
92.0 TL3
bp 165
bp 110
bp 125
TL3
TL3 US
TL3 US
Voltage
Voltage
Voltage
U
: 630V
U
: 270V /
U
: 480V
N
N
N
480V
-
-
-
≥ 630
≥ 480
≥ 475
599
456
450
567
432
430
536
408
404
Under voltage
U
derating
V
R
T
380
340
300
U [V]
Under voltage
U
derating
V
R
T
380
340
300
U [V]