Kaco blueplanet 92.0 TL3 US Manual page 67

Grid support interactive inverter
Table of Contents

Advertisement

Manual
Country-
Level Display/
spec. Set-
settings
tings
Lock-In voltage
1
2
3
4
4
10 – 126.6 [%
Unom] /
Unom] /
Lock-Out voltage
1
2
3
4
4
10 – 126.6 [%
Unom] /
Unom] /
Power gradient in-
1
2
3
4
4
creasing & power gra-
dient decreasing
1 – 65,534 [% Slim /
min] /
Settling time
1
2
4
4
3
1000 – 12000 [ms] /
5000 [ms] /
Number of nodes
1
2
3
4
4
2 - 10
Node 1- Node 10
1
2
3
4
4
0-100% [ % Slim] /
0 , 50 , 100 % [ %
Slim] /
0,3 – 1 [ind/cap] /
1 /
0.001
Übererregt | Un-
tererregt
Password protection
Status
Q(P)
3
1
2
4
4
Power gradient in-
4
1
2
3
4
crease& Power gradi-
ent decrease
0 – 65535 [% Slim] /
65535 [% Slim] /
Settling time
1
2
3
4
4
1000 – 12000 [ms] /
5000 [ms] /
Number of nodes
1
2
3
4
4
2 - 10
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Action in this menu/meaning
F Set the voltage above which control is activated.
80 [%
0.1
F Set the voltage below which control is deactivated.
80 [%
0.1
1. Maximum change in the reactive power %S
change to over-excited mode.
2. Maximum change in the reactive power %S
change to under-excited mode.
65,534 /
1
F Einschwingzeit bei einer sprunghaften Änderung des Blindleis-
tungssollwertes einstellen.
10
NOTE: The maximum number of configurable nodes depends
on the selected grid type.
F Specify the number of nodes.
F Power factor for 1st ,10th ... node as a percentage of the maximum
power.
NOTE: For the 1st node, the power must be 0%; for the last
1
node, the power must be 100%. The power values of the
nodes must increase continuously.
F Specify the cos ϕ of the node.
F If a reactive power not equal to 1 is selected: Select the type of
phase shift.
NOTE: Over-excited relates to a capacitive load, under-excited
relates to an inductive load.
1. Activate optional password protection.
2. Confirm the action field.
NOTE:  Define Q(P).
F Set increasing and decreasing power gradient.
1
F Einschwingzeit bei einer sprunghaften Änderung des Blindleis-
tungssollwertes einstellen.
10
NOTE: The maximum number of configurable nodes depends
on the selected grid type.
F Specify the number of nodes.
Configuration and operation | 9
/min in the event of a
lim
/min in the event of a
lim