7 | Installation
7.9.2
Inserting and laying the cables
↻ Time required for connecting the interface cables: 10 min
1. Observe the instructions on the recommended cable for the interface used.
2. Unfasten the cover on the cable fitting [ W_20].
3. Feed the signal cable into the connection area.
ð Signal cable inserted.
Inserting the Ethernet cable
1. Unfasten and remove the cover on the cable fitting [ W_29].
2. Remove the sealing insert.
3. Thread the connection cable through the cover of the cable fitting and the seal-
ing insert.
4. Insert the sealing insert into the cable fitting.
5. Feed the connection cables into the connection area.
ð Ethernet cable inserted.
7.9.3
Connecting via Ethernet
NOTE
The connection plug of an RJ45 cable is larger than the opening of an M25 cable fitting when it is installed. For
this reason, remove the sealing insert before installation and thread the Ethernet cable outside of the cable fit-
ting through the sealing insert.
NOTE
Use a suitable category 7 network cable. The maximum distance between two devices is 100 m (328 ft). The
Ethernet switch allows for the repeater function and supports auto-sensing. Ensure that the cable is correctly
assigned. You can use both crossed and 1:1 protectively-wired Ethernet connection cables.
↻ Connecting cable inside the device.
1. Plug in an Ethernet cable at one of the two Ethernet ports on the communication circuit board.
2. Check that the connecting cable is fitted securely.
ð Connect additional signal cables.
Connecting the device to the network
↻ The Ethernet cable has been connected to the device.
1. Connect the Ethernet cable to the network or a computer.
2. Configure the Ethernet settings and the webserver in the Settings menu.
7.9.4
Connecting the RS485 bus
NOTE
Ensure that the DATA+ and DATA- wires are properly connected. Communication is not possible if the wires are
reversed. Different manufacturers do not always interpret the standard on which the RS485 protocol is based
in the same way. Note that the wire designations (DATA+ and DATA-) for wires A and B may vary from one
manufacturer to another.
Page 34
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Manual
1
Fig. 36: Insert signal cables
1 Cable fitting for routing the Eth-
ernet cable
2 Cable fitting for routing the sig-
nal cable