Kaco blueplanet 92.0 TL3 US Manual page 84

Grid support interactive inverter
Table of Contents

Advertisement

10 | Specifications
Country-
Men
Display/
spec. Set-
u
Setting
tings
level
Cos-phi constant
0,3 – 1 /
0,001
Over-excited | un-
der-excited
Power gradient in-
creasing & power gra-
dient decreasing
1 – 65,534 [% S
min] /
min] /
Settling time
1,000 – 120,000
[ms] /
10
Q constant
Q constant
0 – 100 [% Slim] /
0[% Slim] /
Under-excited |
over-excited
Output gradient in-
crease & Output gradi-
ent decrease
increasing | decreas-
ing
1 – 65,534 [% S
min] /
min] /
Settling time
1,000 – 120,000
[ms] /
10
Cos-phi(P)
Lock-in voltage
10 – 126.6 [% Unom] /
80 [% Unom] /
[0.1]
Lock-out voltage
10 – 126.6 [%
Unom] /
[%Unom] /
Power gradient in-
creasing & power gra-
dient decreasing
1 – 65,534 [% S
min] /
min] /
Page 84
Action in this menu/meaning
Specified power factor.
1 /
Reactive power mode Under-excited relates to inductive load, over-ex-
cited relates to capacitive load.
Maximum change in the reactive power %S
change to over-excited mode
NOTE: The gradient is overlaid with the settling time.
/
lim
65,534 [% S
/
lim
1
Determines the dynamic behaviour in the event of a change in the cos ϕ
set value. With a reative power change, the cos ϕ is changed according
to a PT-1 characteristic curve with a settling time of 5 Tau.
1,000 [ms]
Set as a percentage of the maximum reactive power.
0.1
Reactive power mode Under-excited relates to inductive load, over-ex-
cited relates to capacitive load.
In addition to configuring the dynamic behavior using the transient time
corresponding to a first-order filter, the reactive power setting can be
determined by a maximum gradient - this means the maximum change
in the reactive power per time period.
Maximum change in the reactive power %S
change to over-excited mode
/
lim
65,534 [% S
/
NOTE: The gradient is overlaid with the settling time.
lim
1
Determines the dynamic behaviour in the event of a change in the Q
target value. With a change of the reactive power or the lock-in and lock
out voltage, the Q is changed according to a PT-1 characteristic curve
1,000 [ms]
with a settling time of 5 Tau.
The control is activated above this voltage.
1
The control is deactivated below this voltage.
80
0.1
Maximum change in the reactive power %S
change to over-excited mode
NOTE: The gradient is overlaid with the settling time.
/
lim
65,534 [% S
/
lim
1
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Manual
/min in the event of a
lim
/min in the event of a
lim
/min in the event of a
lim