Kaco blueplanet 92.0 TL3 US Manual page 89

Grid support interactive inverter
Table of Contents

Advertisement

Manual
10.2.3.1 Parameters for P(U)
Country-
Men
Display/
spec. Set-
u
Setting
tings
level
Operation mode
3
1
2
4
4
OFF | ON
Reference power
Actual power |
Nominal power
Evaluated voltage
1
2
3
4
4
Maximum phase
voltage | Positive se-
quence voltage
Hysteresenmodus
Off | On
Deactivation gradient
0 – 65,534 [% /
min] /
min] /
Deactivation time
0 – 60,000,000
[ms] /
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 – 65,534 [%/Min] /
65,534 [%/min] /
1
Settling time
1000 – 120,000
[ms] /
10 [ms]
Active curve
1
2
3
4
4
1 - 5
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Action in this menu/meaning
F Regelverfahren aktivieren.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
Specifies the power reference for the characteristic. 100 % to be the
nominal power or the actual power at the instant of activation of the
function, the instant when the voltage passes the configured node.
F Select the voltage to be rated.
Defines which voltage in a three-phase system is to be evaluated.
Off: In Non-Hysteresis mode, the active power is increase immediately
in cases of falling voltage.
On: In Hysteresis mode the power is not increased in case of falling volt-
age.
If the available power is above the actual output at the time of deactiva-
tion, the power increase back to the maximum power is limited. The
limitation is implemented by an absolute power limitation that in-
100 [% /
creases with a continuous gradient up to the maximum power. The ac-
1
tual power of the inverter may vary freely below this limit due to a pos-
sible fluctuation in the available power or the target value, but at no
time increases above the absolute power limit.
Only evaluated with activated hysteresis mode: Monitoring time during
which the voltage must remain below the lowest configured node be-
fore the function is deactivated.
100 [ms]
1
Specifies the dynamic response on changing the active power for power
increase. With a voltage change, the active power is changed with the
specified gradient.
The gradient is overlaid with the settling time.
Specifies the dynamic response on changing the active power for power
decrease. With a voltage change, the active power is changed with the
specified gradient.
The gradient is overlaid with the settling time.
Determines the dynamic behaviour in the event of a change in the ac-
tive power set value. With a voltage change, the active power is
changed according to a PT-1 characteristic curve with a settling time of
2,000 [ms] /
5 Tau.
Note: The settling time is overlaid with the increasing and decreasing
gradient.
F Select the active curve.
NOTE: Up to 5 characteristic curves can be configured inde-
pendently and one of them can be activated for regulation
each time.
Specifications | 10
Page 89