9 | Configuration and operation
Country-
Level Display/
spec. Set-
settings
tings
Q(P) Active curve
1
2
3
4
4
1 - 10
Node 1- Node 10
1
2
3
4
4
0-100% [ % Slim] /
0 , 50 , 100 % [ %
Slim] /
0,3 – 1 [ind/cap] /
1 /
0.001
Übererregt | Un-
tererregt
Password protection
Status
Q(U)
3
1
2
4
4
Lock-In power
1
2
3
4
4
0 – 100 [% Slim] /
100 [% Slim] /
Lock-Out power
1
2
3
4
4
0-20 [% Slim] /
[%Slim] /
Lock-In time
1
2
3
4
4
0 – 60,000 [ms] /
30,000 [ms] /
[ms]
Lock-Out time
0 – 60,000 [ms] /
30,000 [ms] /
[ms]
Dead time
1
2
3
4
4
0 -10,000 [ms] /
[ms] /
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] /
Slim / min] /
Settling time
1
2
3
4
4
1,000 – 120,000
[ms] /
10
Page 68
Action in this menu/meaning
F Select active curve.
NOTE: Up to 10 characteristic curves can be configured inde-
pendently and one of them can be activated for regulation
each time.
F Power factor for 1st ,10th ... node as a percentage of the maximum
power.
NOTE: For the 1st node, the power must be 0%; for the last
1
node, the power must be 100%. The power values of the
nodes must increase continuously.
F Specify the cos ϕ of the node.
F If a reactive power not equal to 1 is selected: Select the type of
phase shift.
NOTE: Over-excited relates to a capacitive load, under-excited
relates to an inductive load.
1. Activate optional password protection.
2. Confirm the action field.
NOTE: Define Q(U).
F Set the active power as % of rated power above which control is ac-
tivated.
1
F Set the active power as % of rated power below which control is de-
activated.
5
1
F Set the length of time that the active power must remain above the
lock-in / lock-out power level before control is activated.
1,000
1,000
F Set the intentional delay for the start of the Q(U) function.
0
1
1. Maximum change in the reactive power in the event of a change to
over-excited mode.
2. Maximum change in the reactive power in the event of a change to
under-excited mode.
65534 [%
1
F Set the response speed of the control.
1,000 [ms]
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Manual