9 | Configuration and operation
Country-
Level Display/
spec. Set-
settings
tings
Dynamic reactive cur-
1
2
3
4
4
rent only
Off | On
Dead band mode
1
2
4
4
3
Mode 1 | Mode 2
Reference voltage
4
1
2
3
4
80.0 – 110.0 [%
Unom]
Minimum operating
1
2
4
4
3
voltage activation
45.0 – 125.0 [%
Unom]
Maximum operating
voltage activation
45.0 – 125.0 [%
Unom]
Password protection
Status
Zero current threshold
4
1
2
3
4
undervoltage
0 – 80 [%Unom]
0.1
Zero current threshold
overvoltage
110 – 141.8 [%
Unom]
Reactive current limita-
1
2
3
4
4
tion
0 – 100 [% Imax] /
100 [% Imax] /
Minimum support time
1
2
3
4
4
1,000 – 15,000
[ms] /
10
Enhanced Island Detec-
2
1
3
4
4
tion
Mode
1
2
3
4
4
Off / ROCOF / RO-
COF enhanced / Fre-
quency shift
Password Protection
Page 56
Action in this menu/meaning
NOTE: With FRT mode activated, the pre-fault reactive current
can be added.
F If necessary, activate pre-fault reactive current.
F Select dead band mode for the active control process.
F Set reference voltage for the active control process.
100
0.1
F Set voltage range for the active control process.
0.1 &
0.1
F Set voltage threshold for zero current mode.
If one or more phase/phase or phase/neutral conductor voltages move
below or above the configured threshold, the inverter changes to zero
current mode. The total current is regulated to virtually zero.
0.1
F Set the reactive power limitation.
1
F Set the minimum support time.
5,000 [ms]
NOTE: Grid operators require shutdown of the device with
standalone grid detection. More detailed information at: [See
section 10.5} Page 99]
NOTE: Function is active at the factory and may only be deac-
tivated during island operation (without grid).
1. Select mode and observe menu items.
2. Activate password protection if necessary.
3. Confirm action field.
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US