11 | Maintenance and troubleshooting
No.
Result message
208 Detection of hardware
detection failed: AC
power board
209 Detection of hardware
detection failed: AC re-
lay board
216 Protect. shutdown HW
- overvoltage DC link
halves
217 Protect. shutdown HW
- 24V supply voltage
224 External limitation
225 Battery voltage too low N/A
226 Inverter is manually
disconnected from the
grid
227 Protective shutdown
current asymmetry
228 Protective shutdown
voltage asymmetry
230 AC voltage limitation
231 External active power
value
NOTE
Event number not found?
Event numbers that are displayed in the device and not listed here generally require a service call by your in-
stallation partner.
Page 116
Explanation
The data saved on the AC power board is
erroneous.
The data saved on the AC relay board is
erroneous.
One of the two DC link halves has ex-
ceeded the maximum value. Shutdown
occurs by way of HW-detection and Trip-
Zone shutdown.
The supply voltage in the device has ex-
ceeded its max. permitted value. Shut-
down occurs by way of HW-detection and
TripZone shutdown.
This is a relative specification of the de-
sired active power adjustment.
The device can be disconnected from the
grid manually after logging in via the web
user interface. This message then ap-
pears.
Protective shutdown that enables safe
shutdown of the device in the event of
(high-ohm) grid failures. Grid events can
cause asymmetrical currents in the in-
verter. They are detected and shut down
accordingly.
Protective shutdown that enables safe
shutdown of the device in the event of
(high-ohm) grid failures. Grid events can
cause asymmetrical voltages in the in-
verter. They are detected and shut down
accordingly.
This is a protective function of the device
that allows it to be switched off quickly in
case of incidents or switching operations
at the medium voltage level.
External specification of a setpoint value
for the fed-in active power. The fed-in ac-
tive power can be increased or decreased
with the grid support procedure. Grid
support procedures thereby have a
higher priority.
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Manual
Remedy
See remedy in Status 207
See remedy in Status 207
Restart of the device attempted? (Discon-
nect AC/DC - switch it back on after 5
minutes.)
=> If unsuccessful, contact Service.
Restart of the device attempted? (Discon-
nect AC/DC - switch it back on after 5
minutes.)
=> If unsuccessful, contact Service.
N/A
N/A
Activate the grid connection via the icon
on the web user interface.
If this occurs repeatedly, contact Service. -
See remedy in Status 227
Normative requirement of the grid opera-
tor
Normative requirement of the grid opera-
tor
Pers.
B
B
B
B
-
-
B
-
-
-