Kaco blueplanet 92.0 TL3 US Manual page 41

Grid support interactive inverter
Table of Contents

Advertisement

Manual
For commissioning, a DC supply of the KACO unit is sufficient.
Required components
– Wifi-enabled notebook, tablet, or smartphone (use of Android, or iOS devices possible).
– USB WiFi stick (KACO accessories, type: WLAN adapter Digitus 150N micro Article no.: 3013222)
Establishing a connection to the KACO device via WiFi
F Connect the USB WiFi stick to the device and connect to the access point generated by the device using a notebook or
mobile device. Every device generates a unique AP-name based on its serial number so that it is possible to install sev-
eral devices at the same time if multiple WiFi sticks happen to be available..
F Name of access point: <Device designation serial number> (e.g. "bp87-<serial number>" or "bp150-<serial number>")
1. Password: kacowifi
2. Launch the browser on the terminal device and enter server name a) or server address b):
F http:// 192.168.1.1
F Confirm entry.
ð The device configuration page is displayed.
1. At the Login/register icon, log in as:
2. User name: user
3. Password: kaco-user
8.4.2
Start-up via LAN connection
MODBUS RTU
RS485
STRING
DC
COMBINER
Fig. 47: Start-up via Ethernet
Application
The planned network infrastructure or AC-coupling is not yet in place or has not been completed.
Required components
– Notebook with Ethernet interface
– Ethernet cable (uncrossed patch cable)
Establishing a connection to the KACO device
1. The device must be opened in order to connect the Ethernet cable! For safety reasons, KACO therefore recommends
establishing a connection via WiFi.
2. The device's communication circuit board has 3 Ethernet ports that can be used:
1. The 2 neighboring shielded Ethernet ports are marked LAN1 and LAN2. These ports have an internal switch and, in
their factory default state, they expect to receive an IP address from a DHCP server. As such, these can only be used if
the connected PC makes a DHCP service available.
2. The port marked CON700 that can be used to speak to the device using the static IP address 169.254.1.1. This option
is preferable if you have decided to go with a wired solution.
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
LAN2
INVERTER
LAN1
Ethernet Port 0
(Static IP)
CON700
Notebook
Ethernet
Start-up | 8
Fig. 46: Login screen
Ethernet
Notebook
Page 41