Kaco blueplanet 92.0 TL3 US Manual page 44

Grid support interactive inverter
Table of Contents

Advertisement

8 | Start-up
STRING
COMBINER
STRING
COMBINER
STRING
COMBINER
Fig. 49: Start-up via Segment Controller
Scope of application
The network infrastructure already exists. All of the KACO devices in the segment can be reached via Ethernet using a Seg-
ment Controller.
NOTE: When multiple Segment Controllers are present, keep in mind that the Segment Controllers can-
not be connected to one another via the network during start-up.
Once start-up is complete (assignment of the devices to individual segment controllers) they can be connected in the net-
work by means of a Main network switch.
Required components
– Notebook with Ethernet interface and pre-prepared start-up configuration file
– Segment Controller
Procedure
1. Connect the notebook to the Segment Controller via Ethernet (or to a switch that provides access to the Segment
Controller).
2. Upload a pre-prepared device configuration (e.g. a device configuration that has been set up successfully on a single
device).
3. Using the Segment Controller's WEB server, it is then possible to display and select all of the connected devices on
the Segment Controller that should have this configuration.
4. Once the configuration has been uploaded to the respective devices, they will go into operation automatically follow-
ing a restart.
10
Note: Otherwise all inverters would be visible for the respective Segment Controller.
Page 44
INVERTER
INVERTER
Up to 45
INVERTER
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Manual
Ethernet
Ethernet
Ethernet
Segment Controller *)
Ethernet
*): MC blue'Log
10
Notebook