Kaco blueplanet 92.0 TL3 US Manual page 43

Grid support interactive inverter
Table of Contents

Advertisement

Manual
Establishing a connection to the KACO device
1. The device must be opened in order to connect the Ethernet cable! The device has 3 Ethernet ports that can be used.
These are located on the printed-circuit board marked . In this application only one of the 2 neighbouring shielded
Ethernet ports (marked LAN1 and LAN2) should be used. These ports have an internal switch and, in their factory de-
fault state, they expect to receive an IP address from a DHCP server.
. NOTE: Please do not under any circumstances connect the Ethernet cable to the unshielded RJ45 slot
marked J200 as this typically causes damage to the printed circuit board!
2. Use a functioning Ethernet slot on the external network end.
3. It may be necessary to take additional IT configuration measures in the external network so that the device is as-
signed an IP address.
4. Next, launch the browser on the terminal device and enter the IP address of the device:
ð http://<Geräte-IP-Adresse>
ð The IP address can either be requested from the network administrator or determined using an IP scanner tool.
5. There is also the option of addressing the device using its host name. In its factory default state, the host name con-
sists of a combination of the device derivative designation and the serial number, as shown below:
http://bp125-125TL01234567
F If this is unsuccessful, please use the full domain name:
http://bp125-125TL01234567<ExternalNetworkDomainName> or http://bp87-87-0TL01234567<ExternalNetworkDo-
mainName>
8.4.5
Starting up a plant segment
The following figure provides an example of the structure of a plant segment consisting of a Segment Controller and a cer-
tain number of KACO devices with string combiner (SC) combinations.
9
If the device serial number features a "." dot, then this "." dot is replaced with a "-" dash in the host name as,
according to RFC229, host names must not contain any "." dots.
For local host names, only characters in the range [a-z], [A-Z] and the minus character are permitted.
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
or
http://bp87-87-0TL01234567
Start-up | 8