KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3 S; XL Manual nEnglish translation of German original Authorised electrician Important safety instructions These instructions form part of the product and must be carefully read, observed and stored in a place which is freely accessible at all...
Page 2
Legal provisions The information contained in this document is the property of KACO new energy GmbH. Publication of this document, in whole or in part, is subject to the written consent of KACO new energy GmbH. KACO warranty The latest version of our warranty conditions is available for download at http://www.kaco-newenergy.com.
When working on the PV generator, it is also necessary to switch off the DC voltage with the external DC isolator switch (e.g. at the string combiner or the KACO DC switchbox) in addition to disconnecting the PV generator from the grid.
The potential-free relay contact closes as soon as there is a fault during operation. You use this function, for example, to signal a fault visually or acoustically. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 9...
Page 10
Digital inputs It is possible to enhance the device with additional digital inputs by way of an expansion module (available from KACO Customer Service). This can be used to connect a ripple control receiver or a protective shutdown system.
Cmax of the inverter under all foreseeable conditions. In no condition the design may result in a greater short circuit current than ISCmax of the inverter.Configuring the PV generator [See section 7.6.2} Page 25]. Page 12 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
NOTE: Make sure that the mount is oriented correctly. » Proceed with the installation of the device. Page 18 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
NOTE: Alternatively: At this point, the screw mentioned above can be replaced with a special-purpose screw for protection against theft. » The device is installed. Proceed with the electrical installation. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 19 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
If the type A is used, the insulation threshold must be set to greater than/equal to (≥) 200kOhm in the “DC parameters” menu Configuration via web user interface [See section 9.4.2} Page 49]. For questions regarding the appropriate type, please contact the installer or our KACO new energy cus- tomer service.
Page 26
Otherwise, with the electrolytes present (e.g. Condensation water), the aluminum could be destroyed by the copper bus bars. Page 26 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 27
Otherwise, with the electrolytes present (e.g. Condensation water), the aluminum could be destroyed by the copper bus bars. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 27 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Depending on the local installation specifications, it may be necessary to earth the device with a second ground connection. To this end, the threaded bolt on the underside of the device can be used. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 29...
Within a segment, the KACO devices can be coupled to one another via the integrated switch in an Ethernet daisy chain, whereby the segment controller is connected to the first element of the chain. This topology is displayed in segment 2, for example.
Segment Controller. This configuration is shown as an example in segments 1 and M. As can be seen in the figure, a string combiner is assigned to each KACO device. In terms of communication, these are coupled in directly to the device via an RS485 cable (green cable). MODBUS RTU is used as the communication proto- col for this purpose.
Page 37
It is preferable to install this on a plant component. It is also possible to select an NTP server localized on the internet provided the device has direct access to the internet. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 37...
Page 38
If such an adapter is not available, the other option is to perform an automatic configuration using a USB memory stick. Page 38 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 39
Required components WiFi-compatible notebook, tablet or smartphone (Android or iOS devices can be used). USB WiFi stick (KACO accessory, type: WLAN adapter Digitus 150 N micro article no.: 3013222) Establishing a connection to the KACO device via WiFi 1 Connect the USB WiFi stick to the device and connect to the access point generated by the device using a notebook or mobile device.
Page 40
Ethernet cable (uncrossed patch cable) Establishing a connection to the KACO device 1 The device must be opened in order to connect the Ethernet cable! For safety reasons, KACO therefore recommends establishing a connection via WiFi. 2 The device's communication circuit board has 3 Ethernet ports that can be used: 1.
Page 41
RFC229, host names must not contain any “.” dots. For local host names, only characters in the range [a-z], [A-Z] and the minus character are permitted. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 41...
Page 42
Fig. 57: Start-up via Segment Controller Area of application The network infrastructure already exists. All of the KACO devices in the segment can be reached via Ethernet using a Seg- ment Controller. NOTE: When multiple Segment Controllers are present, keep in mind that the Segment Controllers must not be con- nected to one another via the network during start-up.
Page 43
» Once the parameters have been adopted and the device has been restarted, the device is put into operation. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 43...
The green "Operating" LED is illuminated. Fault No LEDs are illuminated. Fault in the device or AC/DC source Page 44 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 58
F Set the voltage below which control is deactivated. Lock-Out voltage 10 – 124.8 [% Unom] Page 58 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 59
Once the dead time has expired, the control circuit is no longer subject to a delay and the set settling time determines the transient behavior. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 59 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 64
NOTE: Option to reset configured values and the import and export of ment specific parameters. Page 64 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 65
NOTE: Displays all of the actions performed in the system and on the web interface. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 65 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
If the Operating LED and the Feed-in LEDs are flashing slowly and in tandem (~ 1 sec), this indicates that a function has been completed successfully. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 67...
Page 68
Procedure is carried out. Procedure completed. USB stick can be removed. F Remove the USB stick. Page 68 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 69
Notifications / function F Press the right-hand function button (> 5 secs) to commence the procedure. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 69 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 70
NOTE: Device is disconnected from the grid. NOTE: If a button is not pressed within 15 secs: Procedure aborted. Page 70 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Fig. 63: P-Q operating range for bp 165TL3 (Qmax=Smax) Fig. 64: Apparent power subject to the grid voltage for bp165TL3 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 71 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 72
Fig. 71: P-Q operating range for bp 125 TL3 (Q Fig. 72: Apparent power subject to the grid voltage bp 125TL3 Page 72 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 73
Fig. 79: P-Q operating range for blueplanet 92.0TL3 Fig. 80: Apparent power subject to the grid voltage bp 92.0TL3 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 73 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 74
1 s with the transient response of a first-order filter (PT-1) with a time constant of Tau=200ms. The specified displace- ment factor may be configured in the display or via communication, via KACO RS485 protocol and MODBUS/SunSpec. If the applicable grid code requires the cos-φ response to set point by a defined gradient or settling time slower than the configured Tau=200ms, this gradient or settling time must be implemented in the plant control system.
Page 75
Lock-in voltage The control is activated above this voltage. 23 V – 287 V KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 75 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
The device makes use of the following functions in order to regulate the active power. These are described in the follow- ing section: P target value (MPPT/communication) Active power limitation [See section 10.2.1} Page 78] KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 77 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 78
The power reduction parameters can be adjusted in SunSpec model DID123. During this process, you should also check whether internal and/or external power reduction is active. Page 78 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 80
Only evaluated in Hysteresis mode On: Observation time for voltage to remain below lowest configured node before function is deactivated. 0 – 60000000 [ms] Page 80 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 81
, the actual power at the moment of activation. f is the actual frequency and f is the activation threshold as configured. Fig. 92: Equation 3 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 81 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 82
Power reference for power adjustment as in equation 6 and equation 7 with underfrequency for overfrequency incidents. Actual power | Nominal power Page 82 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
If a reduction in power occurs, the power is brought back up to the pre-fault level within 100 ms of the voltage returning. Page 84 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 85
The pre-fault voltage is calculated as a 1-min mean value. Fig. 99: Formula n° 3 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 85 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Some grid connection rules insist that the agreed reactive power be supplied from every operating point of the plant without a reduction in the actual active power. Considering the fact that all KACO TL3 inverters have a semi-circular P-Q operating range, a reduction in the active power is, however, required during operation at maximum active power be- cause an apparent power reserve is not available.
GmbH Service. › The operator can only carry out actions marked with a B. Page 94 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 95
B = Action of the operator; E = The indicated work may only be carried out by an authorized electrician! ; K = The indi- cated work may only be carried out by a service employee of KACO new energy GmbH!
Page 100
See action in the the permitted limit. This limit is country-spe- event of a fault 48 cific. Page 100 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 101
This is not a fault message, it is a status mes- ment from the grid sage. operator. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 101 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 102
If it does -> fault in the device. Page 102 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 103
Switch on AC+DC -> if this is not success- ful, contact the ser- vice department KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 103 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 105
AC grid not possible. DC, wait 1 minute and switch on again. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 105 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 106
(24 V) of the gate drivers is too low. Page 106 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 107
(> 5 sec) [Chapter 9.6.1] or activate the grid connection using the web interface symbol. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 107 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 108
If fault numbers are displayed on the device but are not listed here, then it is usually necessary to have this looked at by your installation partner. Page 108 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
2 Use the lateral openings and lift the device off the mount. » The device has been removed. Proceed with packaging. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 109 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
F Store the device in a dry place, in accordance with the ambient temperature range Environmental data. Page 110 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Service and warranty If you need help solving a technical problem with one of our KACO products, please contact our service hotline. Please have the following information ready so that we can help you quickly and efficiently: Device name / serial number ...
Need help?
Do you have a question about the Blueplanet 87.0 TL3 Series and is the answer not in the manual?