Kaco blueplanet 92.0 TL3 US Manual page 72

Grid support interactive inverter
Table of Contents

Advertisement

9 | Configuration and operation
Country-
Level Display/
spec. Set-
settings
tings
Number of nodes
1
2
3
4
4
2 – 5
Power
0,0 – 100,0 [% Pref] /
100 [% Pref] /
Voltage
80,0 – 125,0
[%Unom] /
0.1
Password protect
Status
Features / Functions
1
2
3
4
4
External grid protection
2
1
4
4
3
disconnection
External grid protection
1
2
4
4
3
Status
Powador-protect
1
2
3
4
4
Powador-protect oper-
ation mode
Auto | On | Off
3rd party device
1
2
3
4
4
3rd party device name
3rd party device opera-
tion mode
On | Off
Password protection
1
2
3
4
4
Status
Page 72
Action in this menu/meaning
F Specify the number of nodes.
F Specify power for 1st, 5th ... Node as a percentage of the maximum
power.
1
1. Specify voltage for 1st, 5th ... node as a percentage of the maximum
voltage.
112 /
2. Activate optional password protection .
3. Confirm the action field.
NOTE: Input screens for advanced device functions
NOTE: Option to detect the external grid protection devices
F Select the device.
NOTE: Configures the grid shutdown via a Powador-protect
connected to the „INV OFF" input of the device.
↻ Auto/On: A Powador-protect is operating in the photovoltaic plant
and is connected to the device at the „INV OFF" input.
F Set the operating mode for Powador-protect.
Auto: The device automatically detects a Powador-protect integrated
into the photovoltaic plant.
On: The digital signal of the Powador-protect must be present at the
digital input of the device for the device to start with feed-in.
Off: The device does not check whether a Powador-protect is integrated
into the PV plant.
NOTE: Configures the grid shutdown via an external device
connected to the digital input of the device
F Enter the name of the external device.
F Select operating mode.
On: The digital signal of the external device must be present on the digi-
tal input so that the device does not shut down.
Off: The device does not check whether an external system is integrated
into the PV system.
1. Option to set password protection.
2. Confirm the action field.