Specifications

10.1

Reactive power control

Reactive power can be used in electrical energy supply networks to bolster the level of voltage. As such, feed-in inverters
can contribute to statistical voltage stability. Reactive power brings about a voltage drop at the inductive and capacitive
components of the equipment which can either bolster or reduce the level of voltage. If the generating plant draws induc-
tive reactive power while active power is being fed in, part of the voltage swing caused by the active power feed can be
compensated for by the supply of reactive power.
This reactive power mode and the respective control process are specified by the grid operator. If no control process has
been specified, then the plant should be operated using a reactive power specification of 0%.
10.1.1 Operating power range depending on grid voltage
The device can be operated within the respective fixed voltage range provided. The maximum apparent power is stated in
the following table. In the event of undervoltage determined by the maximum continuous current subject to the grid volt-
age.
The following figures show the reactive power operating range subject to active power and the apparent power operating
range subject to the grid voltage for various devices.
KACO
KACO
KACO
blue-
blue-
blue-
planet
planet
planet
87.0 TL3
92.0 TL3
105TL3
M1 WM
M1 WM
M1 WM
OD IIF0 /
OD IIG0 /
OD IIG0 /
KACO
KACO
KACO
blue-
blue-
blue-
planet
planet
planet
87.0 TL3
92.0 TL3
105TL3
M1 WM
M1 WM
M1 WM
OD IIFX
OD IIGX
OD IIGX
Voltage
Voltage
Voltage
U
380V
U
400V
U
400V
N:
N:
N:
-
-
-
≥ 380
≥ 400
≥ 380
361
380
361
342
360
342
Tab. 8: Maximum continuous apparent power depending on grid voltage
P [p.u.]
1,2
1
0,8
0,6
0,4
0,2
0
1
0,6
0,0
Fig. 63: P-Q operating range for bp 165TL3 (Qmax=Smax)
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
KACO
KACO
KACO
blue-
blue-
blue-
planet
planet
planet
110 TL3
125 TL3
125TL3
M1 WM
M1 WM
M1 WM
OD IIK0 /
OD IIP0 /
OD IIK0 /
KACO
KACO
KACO
blue-
blue-
blue-
planet
planet
planet
110 TL3
125 TL3
125TL3
M1 WM
M1 WM
M1 WM
OD IIKX
OD IIPX
OD IIKX
Voltage
Voltage
Voltage
U
U
600V
U
480V
N:
N:
N:
270V /
480V
-
≥ 600
≥ 475
≥ 480
545
475
456
520
450
432
492
430
U
660V
N
above 630V
at 595V
at 565V
0,6
1
Q [P.u]
KACO
KACO
KACO
blue-
blue-
blue-
planet
planet
planet
137 TL3
150 TL3
155TL3
M1 WM
M1 WM
M1 WM
OD IIP0 /
OD IIQ0 /
OD IIP0 /
KACO
KACO
KACO
blue-
blue-
blue-
planet
planet
planet
137 TL3
150 TL3
155TL3
M1 WM
M1 WM
M1 WM
OD IIPX
OD IIQX
OD IIPX
Voltage
Voltage
Voltage
U
600V
U
660V
U
N:
N:
N:
-
-
-
≥ 600
≥ 660
≥ 590
570
622
560
540
590
530
S [p.u. S
]
nom
1,2
1
0,8
O
0,6
V
Nominal capability
R
0,4
T
0,2
0
760
720
680
640
600
Fig. 64: Apparent power subject to the grid voltage for
bp165TL3
KACO
Maximum
blue-
apparent
planet
power [p.u.]
165TL3
M1 WM
OD IIQ0 /
KACO
blue-
planet
165TL3
M1 WM
OD IIQX
Voltage
590V
U
630V
N:
-
1,10
≥ 630
1,00
595
0,95
564
0,90
U
Under voltage
V
derating
R
T
560
520
480
U [V]
Page 71