Attach the DRM 0 safety label
According to AS/NZS 4777.2:2015, in Australia PV devices are marked that support
the "Mode 0" remote control command.
1. Attach the supplied safety sticker next to the name plate on the device housing
where it is clearly visible.
2. Please note the Powador-protect application note in the download area on our
homepage. Here you will find the corresponding "Demand Response Modes"
listed in the chapter "Referencing for power control".
8.3

Network topologies

Plant segmentation
Service
Max. 100m
SEGMENT 1
5
Segment
2)
Controller
Network
6
Segment Switch
8
7
(RSTP)
Ethernet
SC
BP1
Ring
SC
BP2
Topology
SC
BP3
9
max. 100m
max. 100 nodes/segment
SC
SC
typ. 10MW/segment
Legend:
SC: String
DC
RS485
Combiner
Fig. 44: Segmentation of a plant
1 Gateway VPN 3G/4G router
2 Main network switch
3 FO - switch (fiber optic)
4 Slicebox (for fiber optic data transfer)
5 Segment Controller
While a gateway to the Internet, a data logger and one instance for the higher-ranking power control are generally suffi-
cient in smaller systems, larger systems must be divided into separate network segments because there are certain limits
with regard to the number of manageable nodes for monitoring/control.
This figure shows a potential alternative for multiple segments. Depending on the local circumstances, it may be more fa-
vorable to position the components differently (e.g. positioning the segment controller centrally and connecting
the segment switch via glass fiber cable).
Located directly after the Gateway VPN-Router, is the main network switch via which the segment con-
troller is connected in. With the corresponding system size (distance from main network switch to the seg-
ment controller >100 m), it may also be necessary to connect in segments that are further away via a glass fiber
connection.
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
User
HTTP(S)
10
Plant
1)
Controller
2
Main Switch
SEGMENT 2
Segment
Controller
HTTP(S)
FTP
MODBUS/RTU
Ethernet
SC
BP1
BPm
SC
REST
SC
BP2
BPk
SC
Topology
SC
BP3
BPj
SC
max. 100m
SC
BP: blueplanet
RSTP: Rapid Spanning Tree
Inverter
Protocol
Start-up | 8
HTTP(S)
Internet
XMPP
REST
1
Gateway
VPN 3G/4G Router
3
Fiber
FO Switch
Splicebox
2)
MQTT
MODBUS/TCP
BPk
SC
Line
BPj
SC
BPi
SC
SC
MQTT: Messge Queuing
REST: Representational State
Telemetry Transport
Transfer (direct cloud comm.)
6 Network segment switch
7 Inverter
8 String combiner
9 Connection cable and protocol
- DC / Modbus RTU / RS485
10 Plant Controller
Fig. 43: Sticker DRM 0 for Australia
Cloud
meteocontrol Portal
WEB-
Database-
App-
Server
Server
Server
4
Splicebox
FO Switch
SEGMENT M
Segment
2)
Controller
Network
Segment Switch
(RSTP)
Ethernet
SC
BP1
BPk
Ring
SC
BP2
BPj
Topology
SC
BP3
BPi
max. 100m
SC
SC
1): meteocontrol blue'Log XC
2): meteocontrol blue'Log XM
SC
SC
SC
Page 39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Blueplanet 110 tl3 usBlueplanet 125 tl3 us

Table of Contents