Kaco blueplanet 92.0 TL3 US Manual page 86

Grid support interactive inverter
Table of Contents

Advertisement

10 | Specifications
Country-
Men
Display/
spec. Set-
u
Setting
tings
level
Lock-Out time
0 – 60,000 [ms] /
30,000 [ms] /
[ms]
Downtime
1
2
3
4
4
0 -10,000 [ms] /
[ms] /
Output gradient in-
crease & Output gradi-
ent decrease
increasing | decreas-
ing
1 – 65,534 [% S
min] /
min] /
Settling time
1,000 – 120,000
[ms] /
10
Min. cos-phi Q1 - Min.
cos-phi Q4
0 – 1 /
0,001
Q1
Q4
Q2
Q3
Priority mode
Q priority | P priority
Active curve
1 – 4 / curve 1 TMP /
curve 2 / curve 3 /
curve 4
Number of nodes
2 – 10
1. Stützstelle ... 10.
Stützstelle
Power | Voltage |
Excitation
0 – 100 [% S
43.6 [% S
Page 86
Action in this menu/meaning
Length of time that the active power must remain below the lock-out
power level before control is deactivated.
1,000
If the voltage switches from a characteristic curve section with Q=0 to a
characteristic curve section with Q≠0 under active control, then the re-
0
active power setting process is delayed by the set dead time. Once the
1
dead time has expired, the control circuit is no longer subject to a delay
and the set transient time determines the transient behaviour.
In addition to configuring the dynamic behavior using the transient time
corresponding to a first-order filter, the reactive power setting can be
determined by a maximum gradient - this means the maximum change
in the reactive power per time period.
Maximum change in the reactive power %S
change to over-excited mode
/
lim
65,534 [% S
/
NOTE: The gradient is overlaid with the settling time.
lim
1
Settling time in the event of an abrupt change in the reactive power tar-
get value (e.g. caused by a voltage jump). The transient behavior corre-
sponds to a first-order filter (PT-1) with settling time = 5 Tau.
2,000 [ms]
NOTE: The settling time is overlaid with the increasing and de-
creasing gradient.
In the event of a significant voltage deviation, the maximum reactive
power adjustment range can be limited by a minimum cos ϕ in order to
prevent an excessive reactive power supply and, as a result, a significant
0 /
reduction in the maximum active power that can be fed in.
Minimum cos ϕ in over-excited operating mode (in-feed).
Minimum cos ϕ in under-excited operating mode (in-feed).
Minimum cos ϕ in over-excited operating mode (charge).
Minimum cos ϕ in over-excited operating mode (charge).
P priority can be selected as an alternative to the standard setting Q pri-
ority. When it comes to P priority, the reactive power adjustment range
is limited subject to the limited apparent power of the inverter and the
active power that is currently available and fed in.
Up to four characteristic curves can be configured independently and
one of them can be activated for regulation each time.
Specify the number of nodes for the Q(U) characteristic curve.
Power of the node as a percentage of the maximum power.
For the 1st node, the power must be 0%; for the last node, the power
must be 100%. The power values of the nodes must increase continu-
ously.
] /
lim
] /
0.1
lim
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US