Reactive power control

Reactive power can be used in electrical energy supply networks to bolster the level of voltage. As such, feed-in
inverters can contribute to statistical voltage stability. Reactive power brings about a voltage drop at the induc-
tive and capacitive components of the equipment which can either bolster or reduce the level of voltage. If the
generating plant draws inductive reactive power while active power is being fed in, part of the voltage swing
caused by the active power feed can be compensated for by the supply of reactive power.
This reactive power mode and the respective control process are specified by the grid operator. If no control
process has been specified, then the plant should be operated using a reactive power specification of 0%.
10.1.1 Operating power range depending on grid voltage
The device can be operated within the respective fixed voltage range provided. The maximum apparent power
is stated in the following table. In the event of undervoltage determined by the maximum continuous current
subject to the grid voltage.
The following figures show the reactive power operating range subject to active power and the apparent power
operating range subject to the grid voltage for various devices.
bp 87.0
bp 92.0
TL3
TL3
Voltage
Voltage
U
: 380V
U
: 400V
N
N
-
-
≥ 380
≥ 400
361
380
342
360
323
340
Tab. 8: Maximum continuous apparent power depending on grid voltage
P [p.u.]
1,2
1
0,8
0,6
0,4
0,2
0
1
0,6
0,0
underexcited
Fig. 61: P-Q operating range for bp 87.0 TL3 (Q
P [p.u.]
1,2
1
0,8
0,6
0,4
0,2
0
1
0,6
0,0
underexcited
Fig. 63: P-Q operating range for bp 92.0 TL3 (Q
Page 74
bp 105
bp 125
bp 137
TL3
TL3
TL3
Voltage
Voltage
Voltage
U
: 400V
U
: 600V
U
: 600V
N
N
N
-
≥ 600
-
≥ 380
545
≥ 600
361
520
570
342
492
540
323
464
510
U
380V
N
above U
N
at 0,95 U
N
at 0,9 U
N
at 0,85 U
N
0,6
1
Q [P.u]
overexcited
=S
)
max
max
U
400V
N
above U
N
at 0,95 U
N
at 0,9 U
N
at 0,85 U
N
0,6
1
Q [P.u]
overexcited
=S
)
max
max
Manual
bp 150
bp 155
bp 165
TL3
TL3
TL3
Voltage
Voltage
Voltage
U
: 660V
U
: 590V
U
: 630V
N
N
N
-
-
-
≥ 660
≥ 590
≥ 630
627
560
599
590
530
567
561
502
536
S [p.u. S
]
nom
1,2
1
0,8
0,6
Nominal
Disconnection
OVRT
capability
0,4
0,2
0
580
540
500
460
420
Fig. 62: Apparent power subject to the grid voltage for bp
87.0 TL3
S [p.u. S
]
nom
1,2
1
0,8
0,6
Nominal
Disconnection
OVRT
capability
0,4
0,2
0
580
540
500
460
420
Fig. 64: Apparent power subject to the grid voltage for bp
92.0 TL3
KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
bp 110
bp 125
Maximum
TL3 US
TL3 US
apparent
Voltage
Voltage
power [p.u.]
U
:
U
: 480V
N
N
270V /
480V
-
-
1,10
≥ 480
≥ 475
1,00
456
450
0,95
432
430
0,90
408
404
0,85
Under voltage
U
derating
V
R
T
380
340
300
U [V]
Under voltage
U
derating
V
R
T
380
340
300
U [V]

Advertisement

Table of Contents
loading

This manual is also suitable for:

Blueplanet 125 tl3Blueplanet 110 tl3 us

Table of Contents