4 | Technical data
blueplanet
AC Output levels
Nominal power
Nominal voltage
Voltage range: continuous op-
eration
Nominal current
Max. continuous current
Contribution to peak short-cir-
cuit current ip
Initial short-circuit alternating
current (lk" first single-period
effective value)
Short circuit current continu-
ous [ms] (max output fault
current)
Inrush current
Nominal frequency
Frequency range
Reactive power
cos phi
Number of feed-in phases
Distortion factor (THD)
Max. voltage range (up to 100
s)
AC overvoltage protection
blueplanet
Max. efficiency
European efficiency
CEC efficiency
Self consumption: Standby
Infeed from
Protection class / over voltage
category
Transformer
Grid monitoring
Distribution system
Page 16
92.0 TL3
92 kVA
400 V (3P+PE)
300 V - 460 V
3 x 132.3 A
3 x 132.3 A
193 A
137 A
134 A
500 V
92.0 TL3
98.9 %
98.6 %
98.6 %
TN-C system, TT system, Solid grounded wye
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Manual
110 TL3 US
Output levels (AC)
110 kVA
480 V (3P+PE)
300 V - 552 V
3 x 132.3 A
5 A [RMS (20ms)]
50/60 Hz
45 - 65 Hz
0-100 % Snom
0.3 - 1 ind/cap
3
< 3 %
600 V
Base
110 TL3 US
99.1 %
98.8 %
98.8 %
< 10 W
> 200 W
I / III (AC) II (DC)
no
Country-specific
125 TL3 US
125 kVA
300 V - 552 V
3 x 150.5 A
3 x 152 A
260.8 A
150.8 A
150 A
125 TL3 US
98,98 %
98.73 %
98.70 %