| Legal provisions Manual Legal provisions The information contained in this document is the property of KACO new energy GmbH. Publication of this document, in whole or in part, is subject to the written consent of KACO new energy GmbH. KACO warranty For current warranty conditions contact your system integrator.
Manual Contents Photovoltaic feed-in inverter 8.2 Preconditions relating to standards ....37 Contents 8.3 Network topologies........38 1 General information ........... 8.4 Start-up options ..........39 1.1 About this document ........9 Configuration and operation ....... 44 1.2 More information .......... 9.1 Initial start-up..........
– When working on the PV generator, it is also necessary to switch off the DC voltage with the external DC isolator switch (e.g. at the string combiner or the KACO DC switchbox) in addition to disconnecting the PV generator from the grid.
The potential-free relay contact closes as soon as there is a fault during operation. You use this function, for example, to signal a fault visually or acoustically. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 9...
Page 10
In addition to the safety functions, the internal interface switches can also be actuated via the "Inverter Off" input. If a Powador-protect is used as the central interface protection, the fail-safe disconnection of suitable KACO inverters from the public grid can be carried out by the internal interface switches instead of separate interface switches. This re- quires the inverters in the photovoltaic system to be connected to the Powador-protect.
– Close to the ground, accessible from the front and sides without requiring additional resources. – In outdoor areas, KACO new energy recommends protecting the device from direct weather exposure and sunlight. This should be carried out by means of constructional measures (e.g. wind breaks) in order to reduce thermal heating of the components, premature derating and more extensive wear of the fans.
3. Be mindful of the weight of the device and use aids to secure it. Page 20 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet...
Page 23
2. Prior to installation, check the inner area for condensation and if necessary, allow it to dry sufficiently before installa- tion. 3. Immediately remove any moisture from the housing. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 23 blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blue-...
If the type A is used, the insulation threshold must be set to greater than/equal to (≥) 200 kOhm in the “DC parameters” menu [see [See section 9.4.2} Page 52]]. For questions regarding the appropriate type, please contact the installer or our KACO new energy customer service.
Page 28
96 mm extends into the cable gland to ensure proper function and use [See figure 28 [} Page 29]. Page 28 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet...
Page 29
Otherwise, the aluminium may be destroyed by the copper busbars in the presence of electrolytes (e.g. con- densate). KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 29 blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blue-...
Depending on the local installation specifications, it may be necessary to earth the device with a second ground connection. To this end, the threaded bolt on the underside of the device can be used. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 31...
Page 33
Note that the wire designations (DATA+ and DATA-) for wires A and B may vary from one manufacturer to another. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 33 blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blue-...
Page 34
1. Loosen the cable fitting to pass the signal cable through [ W_20] Page 34 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet...
Page 35
6. After commissioning: Configure the external device Overvoltage protection in the menu entry Properties / functions. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 35 blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blue-...
>100 m), it may also be necessary to connect in segments that are further away via a glass fibre connec- tion. Page 38 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3 KACO blueplanet 155 TL3 KACO blueplanet 165 TL3...
Commissioning | 8 Within a segment, it is possible to link KACO devices to one another as part of an Ethernet daisy-chain by way of an integ- rated switch, whereby the Segment Controller is connected at the first element in the chain. For this purposes of an ex- ample, this topology is shown in segment 2.
Page 40
– Ethernet cable (uncrossed patch cable) Establishing a connection to the KACO device 1. The device must be opened in order to connect the Ethernet cable! For safety reasons, KACO therefore recommends establishing a connection via WiFi. 2. The device's communication circuit board has 3 Ethernet ports that can be used: Page 40 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO...
Page 41
ð Once the parameters have been adopted and the device has been restarted, the device is put into operation. 8.4.4 Starting up a network The following figure provides an example of the structure of a KACO device with string combiner (SC) and external net- work connection MODBUS RTU...
Page 42
For local host names, only characters in the range [a-z], [A-Z] and the minus character are permitted. Page 42 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet...
Page 43
Fig. 50: Start-up via Segment Controller Area of use The network infrastructure already exists. All of the KACO devices in the segment can be reached via Ethernet using a Seg- ment Controller. NOTE: When multiple Segment Controllers are present, keep in mind that the Segment Controllers must not be connected to one another via the network during start-up.
Page 45
It is preferable to install this on a plant component. It is also possible to select an NTP server localized on the internet provided the device has direct access to the internet. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 45...
The green "Operating" LED is illuminated when AC and DC voltage is present. Page 46 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3 KACO blueplanet 155 TL3 KACO blueplanet 165 TL3...
Page 47
Note: The procedure will last up to 5 min for firmware updates or up to 30 secs for parameter updates. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 47 blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blue-...
We recommend using an up-to-date Firefox or Chrome browser or the default browser that is available on the mobile terminal devices to configure the device via the web interface. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 51...
However, if the interface protection setting limits the voltage-time characteristic curve, then the interface protection will trip and interrupt the ride-through as configured. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 91...
Some grid connection rules insist that the agreed reactive power be supplied from every operating point of the plant without a reduction in the actual active power. Because KACO devices have the full P-Q operating range, a reduction in the active power is, however, required during operation at maximum active power because an apparent power reserve is not available.
– If fast auto-reclosure is used in a distribution grid and the deactivated part of the grid remains live as an island, reclos- ure will likely happen during phase displacement which might cause damage to rotating machinery on the grid. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 97...
Enhanced island detection method The new method by KACO new energy, enhanced island detection, employs a strategy to reliably detect island formation that is based on the characteristic differences between an interconnected grid and an islanded grid, thus ensuring reliable fast detection and prevention of false tripping.
Page 99
(1) Normal operation: Active power and reactive power provision at different voltages. (2) Q on Demand function: Reactive power provision at nominal grid voltage outside feed-in mode. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 99...
2. Disconnect the DC side using the external DC isolator switch. . DANGER! The DC cables are still live KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO Page 103 blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blue-...
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched. 1. If a fault occurs, notify an appropriately authorized and qualified electrician or KACO new energy GmbH Service.
F Store the device at a dry location, in accordance with the ambient temperature range [See section 4.3} Page 15]. Page 118 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet...
Manual Service and warranty If you need help solving a technical problem with one of our KACO products, please contact our service hotline. Please have the following information ready so that we can help you quickly and efficiently: – Device name / serial number –...
Page 122
Unauthorised modifications to the supplied devices and/or any use of the devices that is contrary to their intended use render this Declaration of Conformity null and void. This Declaration of Conformity is issued under the sole responsibility of KACO new energy GmbH. Page 122 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO...