Bidirectional feed-in inverter m, l, xl version (148 pages)
Summary of Contents for Kaco blueplanet 92.0 TL3 US
Page 1
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US S, XL - Grid Support Interactive Inverter Manual nEnglish translation of German original Authorized electrician Important safety instructions These instructions form part of the product and must be carefully read, observed and stored in a place which is freely accessible at all...
Page 2
| Legal provisions Manual Legal provisions The information contained in this document is the property of KACO new energy GmbH. Publication, in whole or in part, requires the written permission of KACO new energy GmbH. KACO warranty The latest version of our warranty conditions is available for download at http://www.kaco-newenergy.com.
EU Declaration of Conformity Certification Country-specific certificates Module-specific certification Layout of Instructions 1.3.1 Symbols used General hazard Fire and explosion hazard Electrical voltage Risk of burns Page 4 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
– Education concerning the installation and start-up of electrical units and plants. – Knowledge of applicable standards and directives. – Knowledge and adherence to this document with all safety notices. Page 6 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
– When working on the PV generator, it is also necessary to switch off the DC voltage with the external DC isolator switch (e.g. at the string combiner or the KACO DC switchbox) in addition to disconnecting the PV generator from the grid.
Page 8
1. In case of maintenance, the device must also be deenergized on the AC-side. 2. We recommend attaching an appropriate hazard warning on the string combiner. Page 8 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 9
1. Pack the device securely for transport. 2. Transport the device using the intended carrying handles of the packaging box. 3. Do not expose the device to any shocks. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 9...
The device is intended for indoor and outdoor applications and may only be used in countries for which it has been ap- proved or for which it has been released by KACO new energy and the grid operator. Operate the device only with a permanent connection to the public power grid. The country and grid type selection must be commensurate with the respective location and grid type.
The potential-free relay contact closes as soon as there is a fault during operation. You use this function, for example, to signal a fault visually or acoustically. Page 12 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 13
In addition to the safety functions, the internal interface switches can also be actuated via the "Inverter Off" input. If a Powador-protect is used as the central interface protection, the fail-safe disconnection of suitable KACO inverters from the public grid can be carried out by the internal interface switches instead of separate interface switches. This re- quires the inverters in the photovoltaic system to be connected to the Powador-protect.
Downloads - Application note "Grid Type and im- pendance requirements …" Grid connection point The clean PV-current is made available at the grid connec- tion point. Page 14 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
IEC 61730 Class A. In no condition the design may result in a greater short circuit current than ISC of the inverter [See section 7.6.2} Page 28]. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 15...
Page 16
Protection class / over voltage I / III (AC) II (DC) category Transformer Grid monitoring Country-specific Distribution system TN-C system, TT system, Solid grounded wye Page 16 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
– Close to the ground, accessible from the front and sides without requiring additional resources. – In outdoor areas, KACO new energy recommends protecting the device from direct weather exposure and sunlight. Realisation through constructional measures (e.g. wind catchers) in order to reduce thermal heating of the compo- nents, earlier derating and greater wear of the fans.
2. The device must be transported and installed by at least 2 persons. DETAIL Z4:1 Fig. 14: Opening the cardboard packaging Fig. 15: Setting the device upright Page 20 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Recommended clearance excluding device:18.70 In Minimum clearance: 11.81 In Minimum clearance: 19.69 In Recommended clearance: 39.37 In ²) Recommended clearance with DC breaker:60,74 In KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 21...
Fig. 19: Fitting the device onto the mount Legend Opening Mounting bracket Center of gravity Mount Lifting and mounting the device ↻ The mount has been installed. Page 22 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 23
2. Check the interior space for any condensation water prior to electrical installation and, if necessary, allow it to dry out sufficiently. 3. Immediately remove any moisture from the housing. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 23...
Fig. 23: Connection area (XL - Version) AC connection point DC connection point AC overvoltage protection base DC overvoltage protection AC earthing bolt PID connection point Page 24 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
All installations must conform to the laws, regulations and standards that are applicable in the country of in- stallation. KACO new energy does not assume any responsibility for compliance or lack of compliance with such laws or codes in connection with the installation of the product.
CU cable lugs with suitable AL/CU washers. Otherwise, with the electrolytes present (e.g. Condensation water), the aluminum could be destroyed by the copper bus bars. Page 26 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 27
If the type A is used, the insulation threshold must be set to greater than/equal to (≥) 200 kOhm in the “DC pa- rameters” menu [see [See section 9.4.2} Page 53]]. For questions regarding the appropriate type, please contact the installer or our KACO new energy customer service.
PV generator The absolute limit for the PV generator is the value of the maximal short circuit current (ISC .) and the maximal open circuit voltage (U ). See Footnote under Electrical data DCmax. Page 28 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 29
1. For the UL market, a larger connection space is required by standard. For this purpose, the DC input plate must be replaced by an external bending box (see chapter Accessories under Technical data). KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 29...
Page 30
CU cable lugs with suitable AL/CU washers. Otherwise, with the electrolytes present (e.g. Condensation water), the aluminum could be destroyed by the copper bus bars. Page 30 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
4. Ensure that all protective elements are properly secured. 1 DC base ð Proceed with the installation of the device. 2 DC overvoltage protection module (3 slots) 3 Jumper KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 31...
Depending on the local installation specifications, it may be necessary to earth the device with a second ground connection. To this end, the threaded bolt on the underside of the device can be used. Page 32 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
9 Ethernet – only for starting up by means of static IP ( [See section 8.4.2} Page 41]) 5 RS485 - default 10 RS485 - connection for string combiner (CON 200) KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 33...
Page 34
Note that the wire designations (DATA+ and DATA-) for wires A and B may vary from one manufacturer to another. Page 34 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 35
The contact is designed as an N/O contact and is labeled "ERR" or "Relay" on the circuit board. Maximum contact load 30 V/1A KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 35...
Page 36
- Connect wire A (+) to wire A (+) and wire B (-) to wire B (-). 6. After commissioning: In the menu item Features / Functions of External Overvoltage protection - Configure external device. Page 36 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
[ T_25/ 44.25 In-Ibs ]. ð The device has been mounted and installed. ð Put the device into operation. Fig. 41: Close the housing cover KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 37...
F Attach the provided safety sticker to the outside of the device housing where it is - Réseau de distribution -Panneux photovoltaïques clearly visible. Fig. 42: Adhesive label UTE_C15-712-1 Page 38 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
With the corresponding system size (distance from main network switch to the seg- ment controller >100 m), it may also be necessary to connect in segments that are further away via a glass fiber connection. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 39...
Manual Within a segment, it is possible to link KACO devices to one another as part of an Ethernet daisy-chain by way of an inte- grated switch, whereby the Segment Controller is connected at the first element in the chain. For this purposes of an ex- ample, this topology is shown in segment 2.
Page 41
– Ethernet cable (uncrossed patch cable) Establishing a connection to the KACO device 1. The device must be opened in order to connect the Ethernet cable! For safety reasons, KACO therefore recommends establishing a connection via WiFi. 2. The device's communication circuit board has 3 Ethernet ports that can be used: 1.
Page 42
The device can also be operated without an external Segment Controller or data logger. In this case however, the internal logging options are limited and log data are only available for a certain period of time. Page 42 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 43
RFC229, host names must not contain any “.” dots. For local host names, only characters in the range [a-z], [A-Z] and the minus character are permitted. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 43...
Page 44
Fig. 49: Start-up via Segment Controller Scope of application The network infrastructure already exists. All of the KACO devices in the segment can be reached via Ethernet using a Seg- ment Controller. NOTE: When multiple Segment Controllers are present, keep in mind that the Segment Controllers can- not be connected to one another via the network during start-up.
It is only possible to configure the grid parameters with DC voltage. The further parameters can also be config- ured with a present AC voltage. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 45...
Page 46
It is preferable to install this on a plant component. It is also possible to select an NTP server localized on the internet provided the device has direct access to the internet. Page 46 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
LED flashing LED not illuminated Operating status LED status Description Start The green "Operating" LED is illuminated when AC and DC voltage is present. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 47...
Page 48
Note: The procedure will last up to 5 mins for firmware updates or up to 30 secs for parameter updates. Page 48 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
However, the measuring elements ensure maximum solar yield. Due to these tolerances, the daily yields shown on the display/screen may deviate from the values on the grid operator’s feed-in meter by up to 15%. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 49...
Page 50
Basic layout - 2nd tab Displays AC and DC voltages Basic layout - 3rd tab Current measurement values with export function Tab. 4: Description of the areas Page 50 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 51
Enables selection of devices connected at the interface. Enables selection of functions in relation to the parameter selected. Tab. 6: Description of the areas KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 51...
If the other device already had protection and the password for the new configuration is dif- ferent, then the new configuration will be rejected. Page 52 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 53
Overview Input screens for basic settings Language 1. Select the required language for the user interface. (14 languages) 2. Confirm the action field. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 53...
Page 54
Off | On Constant voltage 1. Set value for constant voltage control. [See sec- 2. Confirm the action field. tion 4} Page 15] [V] / 1 [V] Page 54 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 55
Constant k negative se- quence swell k 0 – 10 F Set dead band in %. Dead band 2 – 120 [% Uref] 10.0 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 55...
Page 56
COF enhanced / Fre- 1. Select mode and observe menu items. quency shift 2. Activate password protection if necessary. Password Protection 3. Confirm action field. Page 56 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 57
Frequency shift Off | On Pulse period repetition F Define period for detection. time 40 – 6000 [ms] / 1000 [ms] / 1 [ms] KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 57...
Page 58
This percentage relates to the nominal frequency. 1 – 65534 [%/min] / 1. Activate optional password protection. 65534 / 2. Confirm the action field. Password protection Status Page 58 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 59
1. Set waiting time after grid error. failure 2. Activate optional password protection. 1000 - 1800000 3. Confirm the action field. [ms] / 60000 / 1000 Password protection Status KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 59...
Page 60
NOTE: Opportunity to activate standard protective shutdown Trip with intentional 1. If necessary, activate delayed trip-off. delay 2. Activate optional password protection. 3. Confirm the action field. Status Page 60 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 61
45,0– 67.5 [Hz] / 51.5 [Hz] / 0.01 Trip overfrequency time level 2 – 5 0 – 10000000 [ms] / 100 / Password protection Status KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 61...
Page 62
– 5 100 – 125 [% U 114.8 [% U Trip overvoltage time level 2 bis 5 0–120000 [ms] / Password protection Status Page 62 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 63
Enabling the write access allows system critical settings to be changed over Modbus TCP. Really enable write access? F Confirm the action field. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 63...
Page 64
F Enter the value or set the value using the slider. 1,0 – 100,0 [% Slim] / 100[% Slim] / Password protection Status Page 64 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 65
1. Activate option. nect 2. Activate optional password protection. Rampup on first con- 3. Confirm action field. nect Rampup after grid fail- Status KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 65...
Page 66
[ms] / 5,000 [ms] 2. Activate optional password protection. 3. Confirm the action field. Password protection Status Cos-phi (P/Pn) NOTE: Define the cos ϕ (P). Page 66 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 67
Number of nodes NOTE: The maximum number of configurable nodes depends on the selected grid type. 2 - 10 F Specify the number of nodes. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 67...
Page 68
65534 [% Slim / min] / F Set the response speed of the control. Settling time 1,000 – 120,000 [ms] / 1,000 [ms] Page 68 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 69
Actual power | Nominal power Power reference mode with overfrequency Actual power | Nominal power Dynamic gradient F Activate dynamic gradient. mode On | Off KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 69...
Page 70
F Specify the increasing and decreasing output gradient. tion increase & Output gradient limitation de- crease 1 – 65534 [% Slim / min] / 65534 [% Slim / min] / Page 70 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 71
1 - 5 NOTE: Up to 5 characteristic curves can be configured inde- pendently and one of them can be activated for regulation each time. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 71...
Page 72
Off: The device does not check whether an external system is integrated into the PV system. Password protection 1. Option to set password protection. Status 2. Confirm the action field. Page 72 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 73
NOTE: Setting and duration until memory is overwritten: 1 sec [sec] / – 9 days; 10 sec – 92,5 days; 120 sec - 1110 days KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 73...
Page 74
NOTE: The installation wizard is described in the chapter [See sec- tion 8.4} Page 40]. When the installation process is complete, the text: Installation wizard was completed appears Service NOTE: Opportunity to specify the service interval. Page 74 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
3. Open the Settings/Network menu. 4. Assign a unique IP address. 5. Assign a subnet mask. 6. Assign a gateway. 7. Assign DNS server. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 75...
It is only possible to configure the grid parameters with DC voltage. The further parameters can also be config- ured with a present AC voltage. Page 76 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
- Operation mode in the menu on the device or on the web interface. 2. If necessary, allow write access. 3. Set up the Port for access. [Default: 502] ð Access via Modbus enabled. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 77...
U [V] Fig. 67: P-Q operating range for bp 92.0 TL3 (Q Fig. 68: Apparent power subject to the grid voltage for bp 92.0 TL3 Page 78 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 79
U [V] Fig. 75: P-Q operating range for bp 150 TL3 (Q Fig. 76: Apparent power subject to the grid voltage for bp 150 TL3 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 79...
Page 80
If the power factor cos ϕ is specified in the control method, then the deviation relates to the reactive power value brought about by the current power level. Page 80 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 81
The settling time is 1s with the transient response of a first-order filter (PT-1) with a time constant of Tau=200ms. The specified reactive power can be configured on the display or by way of communication via the KACO RS485 protocol and MODBUS/SunSpec.
Page 82
This function ensures that grid support is provided by the reactive power when a significant voltage boost is anticipated due to a high feed level. In this case, a characteristic curve Page 82 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 83
Select the active method for Reactive Power Control (RPC) and define the parameters in the respective method. Cos-phi constant | Q constant | Cos-phi(P/ Plim) | Q(U) | Q(P) Cos-phi constant KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 83...
Page 84
NOTE: The gradient is overlaid with the settling time. 1 – 65,534 [% S min] / 65,534 [% S min] / Page 84 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 85
Length of time that the active power must remain below the lock-in power level before control is deactivated. 0 – 60,000 [ms] / 30,000 [ms] / 1,000 [ms] KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 85...
Page 86
Power | Voltage | must be 100%. The power values of the nodes must increase continu- Excitation ously. 0 – 100 [% S 43.6 [% S Page 86 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
0 – 1000 [s] Sets the time after which the inverter, if WMaxLimPct_RvrtTm it does not receive a new power limit, will cancel it. Timeout KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 87...
Page 88
3 Voltage Voltage Fig. 87: Example characteristic without hysteresis Fig. 88: Example characteristic with hysteresis and a deacti- vation threshold lower than the activation threshold. Page 88 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 89
1 - 5 NOTE: Up to 5 characteristic curves can be configured inde- pendently and one of them can be activated for regulation each time. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 89...
Page 90
The configurability of the function makes it possible to meet a wide variety of standards and grid codes. Certain configura- tion options are not available in some country settings because the applicable standards or grid codes prohibit adjust- ments. Page 90 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 91
1 or 2 is acti- vated. In mode 2, the function is deactivated if the frequency falls below the configured value. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 91...
The protective settings also determine the device’s ability to remain on the grid or not. Protective settings take the upper hand over the capacity of immunity to interference. Page 92 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 93
Eintritt des Ereignisses. Mit der gleichen Dynamik wird während des Ereignisses auf Spannungsänderungen oder bei Ereignissende auf die Spannungswiederkehr reagiert. Der eingespeiste dynamische Blindstrom berechnet sich für das Mit- und Gegensystem gemäß folgender Formel: KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 93...
Page 94
(2) and (4) up to the limit of continuous cur- rent. Page 94 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 95
Mode 2: When calculating the reactive current, the value of the dead band is subtracted from the amount of voltage change. For overvoltage and undervoltage events, formula (4) therefore applies: KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 95...
Some grid connection rules insist that the agreed reactive power be supplied from every operating point of the plant without a reduction in the actual active power. Considering the fact that all KACO TL3 inverters have a semi-circular(PV) full-circular(BI) P-Q operating range, a reduction in the active power is, however, required during operation at maximum active power because an apparent power reserve is not available.
Page 97
10.4.1.1 Parameters for permanent power limitation Country- Display/ Action in this menu/meaning spec. Set- Setting tings level Power limitation Activate or disable the power limitation. Check activation KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 97...
Page 98
This function isn’t active for changes in the power, which are defined by another grid support action such as the return of power after Fault Ride Through, P(f), P(U). Page 98 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Enhanced island detection method KACO new energy's advanced islanding detection, uses a strategy to reliably detect islanding formation that is based on the characteristic differences between an interconnected grid and an islanded grid, thus ensuring reliable fast detection and prevention of false tripping.
(1) Normal operation: Active power and reactive power provision at different voltages. (2) „Q on Demand“ operation : Reactive power provision at nominal grid voltage outside of feed-in operation. Page 100 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
1. Never touch the heat sinks after starting up the device. 2. Wait until a cooling time of at least 10 minutes has elapsed before starting the cleaning process. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 101...
Fig. 105: Removing the cover ð Proceed with the cleaning or removal of the fans. 1 Cover 2 Fastening screw 3 Mounting clips 4 Fans Page 102 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 103
6. Mount the fan grille on the housing. 3 Collar 7. Mount the ventilating plate on the board. 4 Fan ð Interior fan successfully replaced. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 103...
1. Switch off the grid voltage by turning off the external circuit breakers. 2. Disconnect the DC side using the DC isolator switch. . DANGER! The DC cables are still live Page 104 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched. 1. If a fault occurs, notify an appropriately authorized and qualified electrician or KACO new energy GmbH Service.
Page 106
B = Action of the operator; E = The indicated work may only be carried out by an authorized electrician! ; K = The indi- cated work may only be carried out by a service employee of KACO new energy GmbH!
> Is a DC polarity reversal present? => Check polarity according to chapter 7.5. > Is the firmware completely installed? => Reinstall the firmware according to “Soft- ware-Update-Guide xxx”. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 107...
Page 108
(after P(f), restart, after grid error, after every connect) RCD module error A fault has occurred in the all-current sensitive residual current circuit breaker. Page 108 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 109
See explanation in Status 41 See remedy in Status 41 age L2 Grid failure overvoltage See explanation in Status 41 See remedy in Status 41 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 109...
Page 110
This is a requirement of the grid operator. - power reduction. If only reactive power is specified, this message does not appear. Standalone mode Page 110 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 111
Protect. shutdown grid See explanation in Status 81 See remedy in Status 81 volt. L2 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 111...
Page 112
All 3 age protection module must be checked, LEDs light up on the device. and replaced if necessary. The device continues to feed in. Page 112 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 113
164 Error: Filter relay L1 The self-test detected a fault for the relay If this occurs repeatedly, contact Service. - in the device. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 113...
Page 114
See remedy in Status 184 overcurrent L2 int. 186 Protect. shutdown See explanation in Status 184 See remedy in Status 184 overcurrent L3 int. Page 114 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 115
Restart of the device attempted? (Discon- detection failed: Con- roneous. nect AC/DC - switch it back on after 5 trol board minutes.) => If unsuccessful, contact Service. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 115...
Page 116
Event number not found? Event numbers that are displayed in the device and not listed here generally require a service call by your in- stallation partner. Page 116 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Page 117
You must download and send this under the menu item “Service” – “Export Service Package” See table : Config- uration via web user interface [} Page 75] KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 117...
. NOTE: If the DC cable does not fit through the cable fitting due to the size of the cable lug, then the DC cable must be severed at the cable lug. 4. Place protective caps on the ends of the DC cables. Page 118 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
2. Storage in accordance with the technical data > Environmental data ↻ The device is packaged. F Store the device in a dry place, in accordance with the ambient temperature range Environmental data. KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US Page 119...
Device: Do not dispose of faulty devices or accessories together with household waste. Ensure that the old de- vice and any accessories are disposed of in a proper manner. Packaging: Ensure that the transport packaging is disposed of properly. Page 120 KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US...
Service and warranty | 14 Service and warranty If you need help solving a technical problem with one of our KACO products, please contact our service hotline. Please have the following information ready so that we can help you quickly and efficiently: –...