Kaco blueplanet 92.0 TL3 US Manual page 61

Grid support interactive inverter
Table of Contents

Advertisement

Manual
Country-
Level Display/
spec. Set-
settings
tings
Frequency
3
1
2
4
4
Trip underfrequency
1
2
3
4
4
monitoring
Status
Number of trip under-
1
2
3
4
4
frequency levels
1- 5 /
Trip underfrequency
1
2
3
4
4
level 1
45 – 65 [Hz] /
[Hz] /
Trip underfrequency
time level 1
0– 1000000 [ms] /
100 /
1
Trip underfrequency
1
2
3
4
4
level 2 - 5
42.5 – 65 [Hz] /
47.5 [Hz] /
Trip underfrequency
time level 2 – 5
0– 1000000 [ms] /
100 /
1
Trip overfrequency
1
2
3
4
4
monitoring
Status
Number of trip overfre-
1
2
3
4
4
quency levels
1- 5/
Trip overfrequency
1
2
3
4
4
level 1
45.0– 65 [Hz] /
51.5 [Hz] /
Trip overfrequency
time level 1
0 – 10000000 [ms] /
100 /
Trip overfrequency
1
2
3
4
4
level 2 – 5
45,0– 67.5 [Hz] /
51.5 [Hz] /
Trip overfrequency
time level 2 – 5
0 – 10000000 [ms] /
100 /
Password protection
Status
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Action in this menu/meaning
NOTE: Opportunity to monitor frequency trip-off
F Activate if necessary.
F Specify the number of support levels.
2 /
1
NOTE: If the grid frequency is within the deactivation range
for the duration of the deactivation time, then the function is
47.5
deactivated.
0.01
F Define range and trip-off time.
0.01
F Activate if necessary.
F Specify the number of support levels.
2 /
1
NOTE: If the grid frequency is within the deactivation range
for the duration of the deactivation time, then the function is
deactivated.
0.01
1. Define range and trip-off time.
2. Activate optional password protection.
3. Confirm the action field.
1
0.01
1
Configuration and operation | 9
Page 61