Kaco blueplanet 92.0 TL3 US Manual page 65

Grid support interactive inverter
Table of Contents

Advertisement

Manual
Country-
Level Display/
spec. Set-
settings
tings
External
3
1
2
4
4
Power Limitation
1
2
3
4
4
Status
AC fallback active
1
2
3
4
4
power
0 – 100 [%Plim] /
100 [%Plim] /
Fallback time
1
2
3
4
4
0 – 43200 [s] /
300 [s] /
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] /
Slim / min] /
Settling time
1
2
3
4
4
200 – 60,000 [ms] /
1,000 [ms]
Password protection
Status
Power Rampup
2
1
3
4
4
Power rampup gradi-
ent
Gradient
1
2
3
4
4
1 – 600 [% / min] /
10 [% / min] /
Rampup on every con-
1
2
3
4
4
nect
Rampup on first con-
nect
Rampup after grid fail-
ure
Status
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Action in this menu/meaning
NOTE: The output power of the device can be set permanently
to a lower value than the maximum output power by the ex-
ternal power limitation.
F Specify the activation status.
F Set fallback power.
Specifies the standard power in the event of a communication failure. If
no active power command is received within the configured fallback
1
time, the device sets the power to the configured fallback power.
F Set the fallback time for the external power specification.
WARNING! After the set fallback time, external (RS485 or
1
Modbus) specifications for cos-phi, Q and P are reset to the
respective set fallback value (cos-phi constant, Q-con-stant or
fallback power).
NOTE: If the fallback time is set to 0s, external settings for
cos-phi, Q and P are not reset (operation continues with the
last received setpoint).
1. Maximum change in the reactive power in the event of a change to
over-excited mode.
2. Maximum change in the reactive power in the event of a change to
under-excited mode.
65534 [%
1
1. Specify the settling time.
2. Activate optional password protection.
10
3. Confirm the action field.
NOTE: Power ramp-up is used to ramp up the power gradu-
ally. More detailed information at [See section 10.4.2} Page 98]
F Set increase.
1
1. Activate option.
2. Activate optional password protection.
3. Confirm action field.
Configuration and operation | 9