Kaco blueplanet 92.0 TL3 US Manual page 113

Grid support interactive inverter
Table of Contents

Advertisement

Manual
No.
Result message
108 Grid failure overvoltage
L1
109 Grid failure overvoltage
L2
110 Grid failure overvoltage
L3
111 Grid failure undervolt-
age L1
112 Grid failure undervolt-
age L2
113 Grid failure undervolt-
age L3
125 Relay control error
126 AFI measurement tech-
nology error
127 AC voltage measure-
ment technology error
128 Internal memory error
1
129 Power reduction P(U)
148 Error external memory
1
150 Protect. shutdown
drop 1.65V
158 Power limitation
159 Waiting for configura-
tion
160 Error: Grid relay L1
161 Error: Grid relay L2
162 Error: Grid relay L3
163 Error: Grid relay N
164 Error: Filter relay L1
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Maintenance and troubleshooting | 11
Explanation
Device has detected a fault on one phase
and was shut down.
See explanation in Status 108
See explanation in Status 108
See explanation in Status 108
See explanation in Status 108
See explanation in Status 108
The enable signal for the relay control is
read back.
N/A
N/A
Write or read access fault to the internal
RAM.
Message present if the function P(U) sets
the power level according to the specified
parameters subject to the AC voltage.
The device has internal permanent mem-
ories to store the hardware that is used,
for example. The parameters for the op-
eration are derived from there.
Internal protection function to maintain
the required measuring accuracy.
Power limitation because the internal
temperature is too high. The temperature
is measured on the control board. This is
a protective function of the device.
The DSP is waiting for configuration data
from the HMI.
The self-test detected a fault for the grid-
side relay.
See explanation in Status 160
See explanation in Status 160
N/A
The self-test detected a fault for the relay
in the device.
Remedy
Are the settings in the menu according to
the grid voltage correct? => After the
check, visually inspect all connection ter-
minals from the device through to the
grid connection. A fluctuating or missing
AC voltage can indicate this connection
problem.
See remedy in Status 108
See remedy in Status 108
See remedy in Status 108
See remedy in Status 108
See remedy in Status 108
If this occurs repeatedly, contact Service. K
N/A
N/A
Restart of the device attempted? (Discon-
nect AC/DC - switch it back on after 5
minutes.)
=> If unsuccessful, contact Service.
This function can be requested by the
grid operator, for example. If a request is
not present, the function can be deacti-
vated.
Restart of the device attempted? (Discon-
nect AC/DC - switch it back on after 5
minutes.)
=> If unsuccessful, contact Service.
Restart of the device attempted? (Discon-
nect AC/DC - switch it back on after 5
minutes.)
=> If unsuccessful, contact Service.
Check if the device is cooled: Heat sink
clean and installation instructions ob-
served according to the manual (dis-
tances)?
The configuration of the device via the
web user interface must be completely
finished.
If this occurs repeatedly, contact Service. -
See remedy in Status 160
See remedy in Status 160
N/A
If this occurs repeatedly, contact Service. -
Pers.
E
-
-
-
-
-
-
-
B
B
B
B
-
B
-
-
-
Page 113