Kaco blueplanet 92.0 TL3 US Manual page 55

Grid support interactive inverter
Table of Contents

Advertisement

Manual
Country-
Level Display/
spec. Set-
settings
tings
DC starting voltage
2
4
1
3
4
/
[See sec-
tion 4} Page 15] [V] /
1 [V]
Insulation resistance
2
1
3
4
4
100 – 2000 [kOhm] /
300 [kOhm] /
1[kOhm]
AC-Settings
1
4
2
3
4
Country & Grid type
2
4
1
3
4
Nominal grid voltage &
Nominal grid frequency
Password protection
Status
FRT (Fault Ride
2
1
3
4
4
Through)
Operating mode –
1
2
4
4
3
On | Off
Setting | Manual |Pre-
defined zero current
Priority – Reactive cur-
rent limitation | Active
current priority
Constant k positive se-
1
2
3
4
4
quence dip &
Constant k positive se-
quence swell
k 0 – 10
Constant k negative se-
1
2
3
4
4
quence dip
Constant k negative se-
quence swell
k 0 – 10
Dead band
1
2
4
4
3
2 – 120 [% Uref]
10.0
0.1
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Configuration and operation | 9
Action in this menu/meaning
NOTE: The device begins feed-in as soon as this DC voltage is
present.
1. Set the starting voltage.
2. Confirm the action field.
1. Set threshold value at which the insulation monitor reports a fault.
2. Confirm the action field.
Input screens for grid parameters
NOTE: This option influences the country-specific operating
settings of the device. Please consult KACO service for further
information.
1. Select country and grid type.
2. Observe the note for [See section 9.4.2} Page 75]
F Specify optional nominal grid voltage.
NOTE: The device switches off if the grid frequency deviates
from the nominal grid voltage by more than 9.5Hz.
1. Select optional nominal grid frequency.
2. Activate optional password protection.
3. Activate optional password protection.
NOTE: The device supports dynamic grid stabilization (Fault
Ride-Through).NOTICE! More detailed information at [See sec-
tion 10.3} Page 92]
F Select a control process.
On: Activates dynamic grid support using dynamic reactive current.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
F Select a control process.
F Select a control process.
F Set amplification factor k for the pos. sequence for drop and increase
in the grid voltage.
2
0.1
F Set amplification factor k for the neg. sequence for drop and increase
in the grid voltage.
2
0.1
F Set dead band in %.
Page 55