7 | Installation
↻ Connection area cover open.
1. Loosen the cable fitting to pass the signal cable through [ W_20]
2. Thread the connection cables through the cable fitting.
3. Attach the connection cables to the terminals. [See section 7.9.1} Page 33]
4. Tighten cable fitting [ W_20 /
7.9.6
Connecting external grid protection components
Connect the Powador-protect (only in the case of 380/400V
blueplanet 87.0TL3 / 92.0TL3 / 105TL3)
↻ The cable to the external grid protection device is available on the device.
↻ Cover of the device has been opened.
1. Undo the cable fittings [ W_20]
2. Pass the connection cable through the cable fittings.
3. Connect wire A (+) to the terminal marked "INV OFF+" on the first device via the
"DO1" terminal of the protective device.
4. Connect wire B (-) to the terminal marked "INV OFF-" on the first device via the
"GND" terminal of the protective device..
5. Connect the other devices to one another as follows:
- wire A (+) to wire A (+) and wire B (-) to wire B (-).
6. Tighten cable fitting [ W_20 /
7. After commissioning in the menu entry Features / Functions configure the ex-
ternal Overvoltage protection - in Powador-protect.
Connecting a foreign device
NOTE: When using a third-party device, a separate power supply is also
required. Some third-party devices only have a normally closed contact
and do not supply any voltage.
↻ The cable to the external mains protection unit is available on the device.
↻ External power supply is available at the mains protection unit.
↻ Open the cover of the appliance.
1. Loosen the cable glands [ W_20]
2. Guide the connection cable through the cable glands.
3. Connect the corresponding output of the external N/A protection to
"INV_OFF+", observe the operating instructions of the external device.
4. Connect the corresponding output of the external N/A protection to
"INV_OFF"-, -", observe the operating instructions of the external device.
5. Connect the other units together as follows:
- Connect wire A (+) to wire A (+) and wire B (-) to wire B (-).
6. After commissioning: In the menu item Features / Functions of External
Overvoltage protection - Configure external device.
Page 36
13,27 In-Ibs ].
13,27 In-Ibs ]
KACO blueplanet 92.0 TL3 US KACO blueplanet 110 TL3 US KACO blueplanet 125 TL3 US
Manual
Powador-
x
INV
RS485
protect
OFF
A
A
B
A
B
+
-
B
GND
GND
2
1
A
B
y
x
y
RS485
INV
OFF
INV Signal
A
B
A
B
+
-
GND
GND
Fig. 39: Connect the device to
Powador-protect
External
x
INV
RS485
device
OFF
A
A
B
A
B
B
-
+
GND
GND
2
1
y
x
A
B
y
INV
RS485
min./ max.
OFF
10-24V(+/-20%)
/15mA-1A
+
-
A
B
A
B
GND
GND
Activ-Low signal
is required for
switching off
Fig. 40: Connecting the device to
the external grid protection
D01
GND
4
3
2
1
14 NO
11 COM
12 NC
24
21
22
INV OFF
INV ON