Huawei NE05E Hardware Manual page 415

Table of Contents

Advertisement

HUAWEI NE05E,NE08E
Hardware Guide
Table 4-11 Requirements for a network cabinet with natural heat dissipation
where the router is installed horizontally
Supported installation mode
Sets of equipment that can be housed
in the network cabinet
Dimensions (mm): H x W x D
Positions of the air vents on the
network cabinet
Cross-sectional area of the air vents on
the network cabinet (cm
Requirements for
the position where
the router
equipment is
installed in the
network cabinet
Issue 05 (2023-03-31)
2
)
Requirements for
the width
Copyright © Huawei Technologies Co., Ltd.
4 Hardware Installation and Parts Replacement
Horizontal installation
1
NE05E:
200×580×500
NE08E:
100×580×500
NE05E: Air exhaust vents are close to
the top of the network cabinet and
air intake vents are close to the
bottom of the network cabinet.
NE08E: The air intake vent is located
on the left panel of the network
cabinet and the air exhaust vent is
located on the right panel of the
network cabinet.
NE05E: 88
NE08E: ≥230
NE05E: The distance between each
side (left or right side) of the
equipment and the corresponding
side panel of the network cabinet is
at least 40 mm.
NE08E:
● It is recommended that the air
vents on the equipment face the
air vents on the network box, and
the distance between the
equipment and a side panel of the
network box be at least 20 mm. In
this manner, the heat air can be
directly exhausted.
● If air vents are blocked, the
blocked area of the air vents does
not exceed 10% of the total area
of the air vents.
● After installation, the fans on the
equipment are on the left. When
the fans are rotating, the air flows
from left to right, in the same
direction as the air ducts of the
network cabinet.
2
NE05E:
400×580×500
NE08E:
200×580×500
NE05E: 176
NE08E: ≥460
407