Figure 4-2 Internal partition wall of the equipment room
Cleanliness of the Equipment Room
This section describes the requirements for the cleanness of the equipment room.
Issue 05 (2023-03-31)
Requirements
The air conditioner should be installed in the place where the
discharged air from the air conditioner shall not be directed to
the equipment. The air conditioner must be away from a
window to prevent the air conditioner blowing moisture on the
window to devices in the equipment room when the window is
not securely closed.
In addition to the rodent-proof measures (for example,
measures against mice), measures against proliferation of
fungi and mildew should be taken in the equipment room.
When there is high humidity such as on rainy days, do not
open the door of the equipment room to prevent moisture
increase that may be condensed into water on cold surfaces of
the devices in the equipment room.
Storage batteries must be placed separately from devices in
the equipment room.
In the equipment room, do not use organic materials such as
thermal insulation cotton that contains sulfur or chlorine and
rubber gaskets. PEF thermal insulation cotton can be used as a
thermal insulation material.