Interpret Status Indicators

See following diagram and table for information on how to interpret the status indicators.
POINT I/O VHSC Module
Indicator Status for Modules
Status
Off
Flashing green
Green
Module status
Flashing red
Red
Flashing red/green
Off
Flashing green
Green
Network status
Flashing red
Red
Flashing red/green
Off
Input status
Flashing yellow
Yellow
Off
Flashing yellow
Output status
Yellow
Flashing red
Flashing red/yellow
Services
Module status
Network status
Status of input A
Status of input B
0
Status of input Z
1
Status of output 0
Status of output 1
Description
No power applied to device.
Device needs commissioning due to missing, incomplete, or incorrect configuration.
Device operating normally.
Recoverable fault.
Unrecoverable fault – may require device replacement.
Device is in self-test mode.
Device is not online:
- Device has not completed dup_MAC-id test.
– Device is not powered – check module status indicator.
Device is online but has no connections in the established state.
Device is online and has connections in the established state.
One or more I/O connections are in timed-out state.
Critical link failure – failed communication device. Device detected error that prevents it from communicating on the network.
Communication faulted device – the device has detected a network access error and is in communication faulted state. Device
has received and accepted an Identity Communication Faulted Request – long protocol message.
Input is inactive.
Input is toggling On and Off.
Input is active and under control.
Output is inactive.
Output is toggling.
Output is active and under control.
Output is faulted (Open, short, or no output power).
Output is toggling and faulted (possibly open).
Rockwell Automation Publication 1734-IN003I-EN-E - September 2022
POINT I/O 5V DC and 24V DC Very High Speed Counter Module Installation Instructions
Field
PWM safe state value
Counter control SSV
Output control SSV
0
1
Bytes
2
1
1
13