POINT I/O 2 Current and 2 Voltage Input Analog Modules Installation Instructions

Communicate with Your Module

POINT I/O modules send (produce) and receive (consume) I/O data (messages). You map this data onto the processor memory.
These modules produce 6 bytes of input data (scanner Rx) and fault status data. These modules do not consume I/O data (scanner Tx).
Default Data Map
Message size: 6 Bytes
15
14
Input channel 0 – high byte
Input channel 1 – high byte
Produces (scanner Rx)
Status byte for channel 1
OR
UR
Consumes (scanner Tx)
No consumed data
Where:
OR = Overrange; 0 = No error, 1 = Fault
UR = Underrange; 0 = No error, 1 = Fault
HHA = High/High Alarm; 0 = No error, 1 = Fault
LLA = Low/Low Alarm; 0 = No error, 1 = Fault
HA = High Alarm; 0 = No error, 1 = Fault
LA = Low Alarm; 0 = No error, 1 = Fault
CM = Calibration Mode; 0 = Normal, 1 = Calibration mode
CF = Channel Fault Status; 0 = No error, 1 = Fault

Interpret Status Indicators

The following diagram and table show information on how to interpret the status indicators.
1734-IE2C, 1734-IE2CK
Indicator Status for Modules
Indicator
Status
Off
Green
Flashing green
Module status
Flashing red
Red
Flashing red/green
Off
Flashing green
Green
Network status
Flashing red
Red
Flashing red/green
10
13
12
11
10
HHA
LLA
HA
LA
Module status
Network status
Status of input 0
Status of input 1
Description
No power is applied to device.
Device is operating normally.
Device needs commissioning due to missing, incomplete, or incorrect configuration.
Recoverable fault is present.
Unrecoverable fault occurred. Self-test failure present (checksum failure, or ram test failure at cycle power). Firmware fatal error present.
Device is in self-test mode.
Device is not online:
• Device has not completed dup_MAC-id test.
• Device is not powered – Check the module status indicator.
Device is online but has no connections in the established state.
Device is online and has connections in the established state.
One or more I/O connections are in timed-out state.
Critical link failure – Failed communication device. The device has detected an error that prevents it from communicating on the network.
Communication faulted device – The device has detected a network access error and is in communication faulted state. Device has received
and accepted an Identity Communication Faulted Request – Long protocol message.
Rockwell Automation Publication 1734-IN027E-EN-E - June 2023
09
08
07
06
05
Input channel 0 – low byte
Input channel 1 – low byte
Status byte for channel 0
CM
CF
OR
UR
HHA
1734-IE2V, 1734-IE2VK
Module status
Module
Status
Network status
Network
Status
NODE:
Analog
Voltage
Input
Status of input 0
0
Status of input 1
1
1734
04
03
02
01
00
LLA
HA
LA
CM
CF