GuardPLC Relay Output Module

Status Indicators

Indicator
Status
24V DC
On
Off
RUN
On
Flashing
Off
ERROR
On
Off
PROGress
On
Flashing
Off
FORCE
On
Flashing
Off
FAULT
On
Flashing
Off
OSL
Flashing
BL
Flashing
Module status can be interrogated through the programming software. For more information, refer to the
GuardPLC System User Manual, publication 1753-UM001.
Rockwell Automation Publication 1753-IN012C-EN-P - June 2010
Description
24V DC operating voltage present.
No operating voltage.
This is the normal status of the module.
A routine, which has been loaded into the module, is executed.
The module processes input and output signals, carries out communication, and
performs hardware and software tests.
The module is in STOP mode and is not executing a routine.
All system outputs are reset.
STOP mode can be triggered by setting the Emergency stop system variable to TRUE
in the routine, or by direct command from the programming software.
The module is in ERROR_STOP (see ERROR).
• A hardware error has been detected by the module. The module goes to
ERROR_STOP and the execution of the routine is halted. Hardware errors are
errors in the module, errors in one or more of the digital input and output
modules, or errors in the counters.
• A software error in the operating system has been detected by the module.
• The watchdog has reported an error due to exceeded cycle time.
All system outputs are reset and the module ceases all hardware and software tests.
The module can only be restarted by a command from the programming software.
No errors are detected.
The upload of a new module configuration is in progress.
The upload of a new operating system into the nonvolatile ROM is in progress.
No upload of module configuration or operating system in progress.
The module is executing a routine (RUN) and FORCE mode is activated by the user.
The module is in STOP, but Forcing has been initiated and will be activated when the
module is started.
Forcing is OFF.
• The routine (logic) has caused an error.
• The module configuration is faulty.
• The upload of a new operating system was not successful and the operating
system is corrupted.
An error has occurred during a nonvolatile ROM write cycle.
One or more I/O errors have occurred.
None of the above errors has occurred.
Emergency Operating System Loader is active.
Boot Loader unable to load operating system or unable to start COMM operating
system loader.