Network Compatibility

You can use the diagnostic modules with ControlNet, DeviceNet, EtherNet/IP,
or remote I/O networks.
Usage Limitations
Network
1794-IB16D
Remote I/O
Compatible with 1794-ASB
series E (or higher) and
1794-ASB2 series D (or higher)
remote I/O adapters.
DeviceNet
No limitations or constraints.
ControlNet
Direct connection only.
EtherNet/IP
Direct connection only.

1794-IB16D Diagnostic Input Module Compatibility

The 1794-IB16D diagnostic input module interfaces to sensing devices and
detects whether they are on or off. The diagnostic input module converts DC
signals from user devices to the appropriate logic level for use in the FLEX I/O
system. Typical input devices include these types of switches.
• Proximity switches
• Limit switches
• Photoelectric switches
• Selector switches
• Float switches
• Push button switches
When designing a system using a FLEX I/O diagnostic input module, you must
consider:
• the voltage necessary for your application.
• current leakage through the input devices.
• the amount of current consumed by the input devices.
• whether the application requires sinking or sourcing devices.
1794-OB16D
Compatible with 1794-ASB
series D (or higher) and
1794-ASB2 series C (or higher)
remote I/O adapters.
Direct or rack connections.
Direct or rack connections.
Rockwell Automation Publication 1794-UM061B-EN-P - March 2020

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Allen-bradley 1794-ob16d

Table of Contents