Table 48 - Worst Case Reaction Time Calculations
Worst Case Factors
1715 Input Module Delay
1715 Backplane Rate
1715-AENTR Delay
COS=NO
Input Data to ControlLogix
COS=YES
Add-On Instruction Module RPI
ControlLogix SIL2 Task
Watchdog
Add-On Instruction Module RPI
ControlLogix SIL2 Task
Watchdog
Output Data to 1715-AENTR
1715-AENTR Delay
1715 Backplane Rate
1715 Output Module Delay
Using the Add-On
Instruction Data Tags in an
Application Program
Fixed Time
Value
(ms)
15
65
25
1715 Input Module RPI
Fixed
60
AOI Module RPI/2
SIL 2 Task Watchdog
AOI Module RPI/2
SIL 2 Task Watchdog
1715 Output Module RPI
25
65
15
If you are not using COS, the worst-case reaction time from input screw
terminal to output screw terminal is equal to 210 ms plus the following:
- Input RPI
- Output RPI
- Add-On Instruction Module RPI/2
- SIL 2 Task Period x 2
- SIL 2 Task Watchdog x 2
If you are using COS, the worst-case reaction time from input screw terminal
to output screw terminal is equal to 270 ms plus the following:
- Output RPI
- Add-On Instruction Module RPI/2
- SIL 2 Task Period x 2
- SIL 2 Task Watchdog x 2
The following illustrations provide basic examples of how the
Requested_Output_Data tag and the Reconciled_Input_Data tag could be used
in program logic. Data is written to the requested output and read from the
reconciled input, while the raw data in the module-defined input and output
tags is ignored.
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Chapter 8
Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules
User
Configurable
Description
Time (ms)
60
COS = Change of State
30
Value that is entered into the AOI Module_RPI parameter
ControlLogix system runs input module AOI and controls
20
requested output
Assumes requested output in same SIL 2 task as 1715 SIL 2 AOIs
30
Value that is entered into the AOI Module_RPI parameter
ControlLogix system runs output module Add-On Instruction and
20
places requested outputs in output module raw data
80
237