Advertisement

5.10 Wiring Tables and Information

Table 11:
Wiring Table for Initiating Circuits.
Wire Gauge
(AWG)
22
20
18
16
14
12
i
Note:
Maximum loop resistance should not exceed 100 Ohms.
Table 12:
Wiring Table for NACs
ain board NACs are rated for 1.7 amps each. The SGM-1004A NACs are rated for 1.5 amps
M
each.
Total
Signal
Load
Amperes
0.06
2350
0.12
1180
0.30
470
0.60
235
0.90
156
1.20
118
1.50
1.7
i
Maximum voltage drop should not exceed 1.39 Volts for main board and
Note:
1 Volt for SGM-1004A.
Maximum Wiring Run to Last Device (ELR)
ft.
2990
4760
7560
12000
19000
30400
Maximum Wiring Run to Last Device (ELR)
18AWG
16AWG
ft.
m
ft.
716
3750
1143
360
1850
567
143
750
229
71
375
114
47
250
76
36
185
56
94
29
150
46
78
24
125
38
14AWG
m
ft.
m
ft.
6000
1829
8500
3000
915
4250
1200
366
1900
600
183
850
400
122
570
300
91
425
240
73
343
200
61
285
m
910
1450
2300
3600
5800
9200
Max
Loop
Resistance
12AWG
0hms
m
Ohms
2591
30
1296
15
579
6
259
3
174
2
129
1.5
105
1.2
87
1.0
58