18.0
Appendix D: Alarm Verification
Timing
SMOKE DETECTOR
IN ALARM
Reset
3s
These intervals are determined
by the maximum Detector Reset
time, which is 1s for our uses.
A Manual Station, or other contact-closure device, would remain shorted and be detected
during the very short Zone Power burst within the first three seconds. A Smoke Detector will
have been reset, and will require some minimum time to power-up, thus the Verification cycle
will be entered.
113
ULI/ULC Retard / Reset / Restart
60 seconds Maximum
Restart
1s
10s
This interval is determined by the maximum
Detector Start-up time. ULC states a maximum hold
time of 30 seconds.
Appendix D: Alarm Verification Timing
ULI/ULC Confirmation Period
(30s)
60 seconds Minimum
(65s)