Appendix I: Configuration Example Setup
Having the "two stage" option checked, configures the system for a simple two-stage (the mall operation).
The simple two stage puts all output zones into alert for the duration of the Auto GA. Upon expiring the Auto
GA timer, all output zones go into Evac. Alternatively, a subsequent alarm puts all the output zones into Evac
at any time prior to the expiry of the Auto GA timer.
In order to configure the system for a modified two stage, correlated the "Node alarm" status to all the
amplifiers in the system. This will make sure all the amplifiers sound the Alert signal when an initial Alarm is
present in the system. Ensure F2 flag remains blank.
Then, add input zones to represent physical floors of a building.
Ensure you enable the GA flag in the F2 column. This puts the specific zones into Evac upon activation.
134