Each Analog Loop is capable of supporting 159 AP Analog Sensors and 159 AP
Addressable Modules (with a maximum of 99 CLIP sensors and 99 CLIP addressable
modules) which can be wired as Class A, Class X, or Class B.
27 Ampere Power Supply.
Four Class A/B NACs rated at 1.7 Amperes each, which can be configured as Audible or
Visual (silenceable or non-silenceable circuits). Audibles may be steady, Temporal
Code, California Code, or March Time.
Indicating circuits (NACs) may be configured to provide additional auxiliary power or
resettable auxiliary power. NAC expansion using the INX-10A and INX-10ADS.
Fault isolators are present on all in-panel addressable loops.
Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, Assisted
Walk Test.
Outputs for 4 Wire resettable Smoke Power Supply, Auxiliary Power Supply, and an
interface to the Mircom RTI-1 Remote Trouble Indicator.
RS-485 Interface for Remote Annunciators. Remote Annunciators do not occupy a node
on the network. Up to seven annunciators can be connected per node.
Three Level Password Protection with field settable definition which enables the installer
to determine what functions are accessible for each level of password
Four queues for acknowledge with Alarm ACK, Supervisory ACK, Trouble ACK, and
BLDG (Monitor) ACK LED indicators and pushbuttons.
Auxiliary Form-C Relay Contacts for Common Alarm, Common Supervisory, and
Common Trouble.
RS-232 Port for remote system printer or "CRT terminal".
Two Event History Logs; one for Alarm related events and one for all events.
Large 4 line by 20 character alphanumeric, back-lit LCD Display with user-friendly menu
system.
Common Controls and Indicators for System Reset, Lamp Test, Fire Drill, Signal Silence,
General Alarm, General Alarm Acknowledge, AC On, CPU Fault, and Ground Fault.
Two Spare configurable switches and LED Indicators.
16 Zone configurable LED (bi-coloured) Annunciator with slide-in labels for Zone
Description.
Provides drift compensation for ionization and photoelectric smoke detectors
Provides Signal Coding of signal circuits for easy alarm identification (code consists of 1
to 4 digits, each digit consisting of 1-15 pulses on the signal)
Selection for Canadian (ULC) or USA (UL) requirements for Smoke Sensor sensitivity.
Extensive transient protection.
Surface Mountable Enclosures with removable doors for easy installation and service.
Removable Terminal Blocks for easy wiring and service.
Quad Loop Adder module ALCN-792MISO for expanding addressable loops by 2; with
daughter board ALCN-792D expanding addressable loops by a total of 4.
The BBX-FXMNS-6000 enclosure is for the Integrated Fire and Audio consisting of a
backbox, door and middle chassis. Part of this enclosure is the vertical mount telephone
QMT-5302NV and the vertical mount paging microphone QMP-6101NV.
The ANC-6000 Audio Network Controller module includes ARCnet. ARCnet reduces the
wiring for audio and telephone to the ARCnet only or fiber optics (if used).
The RAXN-LCDG is a graphical display remote annunciator.