Figure 29 Main Fire Alarm Control Board Field Terminal Connections (Continued) - Mircom FLeXNet FX-MNS-6000 Installation And Operation Manual

Network fire alarm and emergency communication system
Hide thumbs Also See for FLeXNet FX-MNS-6000:
Table of Contents

Advertisement

Figure 29 Main Fire Alarm Control board Field Terminal Connections (continued)

ANALOG
LOOP 2
CONNECTIONS
(LOOP 0 AND
+
LOOP1 ARE
INTERNAL
-
ADDRESSES
FOR FIRST 8
+
CARDS AND
SECOND 8
-
CARDS
RESPECTIVELY
+
4-WIRE
POWER
-
SUPPLY
+
AUX. POWER
-
(POWER-LIMITED)
TRB
RTI
INTERFACE
TRL
+
NAC 0
INDICATION
+
CIRCUIT 1
(POWER-LIMITED)
-
-
+
NAC 1
INDICATION
+
CIRCUIT 2
(POWER-LIMITED)
-
-
+
NAC 2
+
INDICATION
CIRCUIT 1
(POWER-LIMITED)
-
-
+
NAC 3
INDICATION
+
CIRCUIT 2
(POWER-LIMITED)
-
-
TS2
E+
NAC External Power
I+
Connection
_
i
Note:
ANALOG LOOP FIELD WIRING
(CLASS A OR B)
SEE ANALOG LOOP WIRING SECTION
POWER-LIMITED, 22V DC, 400 mA MAX
Maximum Loop Resistance 40 ohms
POWER-LIMITED, REGULATED
22V DC, 400 mA MAX
5 mV Ripple
RED & WHT
AUXILIARY POWER
FOR REMOTE ANNUNCIATORS
24 VDC SPECIAL APPLICATION
1.7 AMPS MAXIMUM
BLK
RTI
D
POWER-LIMITE
BLU
SUPERVISED NAC # 0
SUPERVISED NAC # 1
SUPERVISED NAC # 2
SUPERVISED NAC # 3
NOT USED
Connect WC-100015 harness
to P10+ and QPS-6650 DCA +
NOT USED
All circuits are power limited (unless marked otherwise) and must use type FPL,
FPLR, or FPLP power limited cable.
NACs are fully supervised and rated for regulated 24 VDC, 1.7A max. They must
be wired as shown in the Wiring Tables and Information on page 58.
CONNECTION TO MIRCOM RTI
REMOTE TROUBLE INDICATOR
(SEE RTI INSTALLATION
INSTRUCTION) BLK TO TRB+ BLU
TO TRL-RED & WHT TO AUX.
POWER COM+
END OF LINE RELAY
LISTED S3403
MODEL A77-716B
4-WIRE
MANUFACTURED BY
DETECTION
SYSTEM SENSOR
DEVICE
+
+
+
TO
3
INITIATING
DETECTION
-
-
-
CIRCUIT
4
+
+
POWER
6
-
-
Legend:
BELL, HORN, OR
STROBE
TS2 Terminal Block is located on the
bottom right corner of the main fire
alarm board.
2
Class B
1
5
CLASS B
WIRING
CLASS A
WIRING
CLASS B
WIRING
CLASS A
WIRING
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
42

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FLeXNet FX-MNS-6000 and is the answer not in the manual?

Table of Contents