13.2.10
Fire Drill Button
The Fire Drill button activates all programmed and non-Disconnected NACs, but does not
transmit any Alarms via the City Tie, or Common Alarm Relay. Fire Drill may be programmed
to operate specific NACs. Fire Drill is cancelled by pressing the button again (toggle switch), or
if the Panel goes into a real Alarm.
13.2.11
Automatic Alm Sig Stop (Ack) Button (Two Stage Only)
If the Panel is not configured for Two Stage Operation, this button does nothing. If the Panel is
configured for Two Stage Operation, activation of the Automatic Alm Sig Stop (Ack) button
while the Auto General Alarm Timer is timing (there is an Alarm in the Panel, but it is still in the
First Stage), that timer is cancelled, and the Automatic Alm Sig Stop (Ack) Indicator is on
steady amber.
13.2.12
General Alarm Button
Activation of the General Alarm button immediately sends the Panel into General Alarm. It will
also re-activate the Signals if they have been Silenced during General Alarm. The General
Alarm condition remains active until the Panel is reset.
13.2.13
Lamp Test Button
Activation of the Lamp Test button turns all front panel Indicators on steady in whichever
colour they would normally be activated and turns the buzzer on steady. If Lamp Test is active
for more than 10 seconds, Common Trouble is activated.
13.2.14
Emergency Voice Control
Request control, press button, Deny control by timeout, Grant press button to transfer control.
Each Node will have an assigned request control and grant button and LED (one button/LED
per Node) to transfer emergency voice control. All Node Request/Grant button and LEDs will
be available at all Nodes. For example if there are 3 Nodes, each Node will have 3 Request/
Grant buttons and LEDs representing all the Nodes 1 to 3.
To gain immediate emergency voice control, press the Node Request/Grant button, LED will
illuminate steady and voice control will be available at that physical Node.
Request Control - press the Request/Grant button at the Node that will be used to provide
emergency voice. The associated Request/Grant button LED will flash at the Node which has
control.
Grant Control - press the Request/Grant button of the requesting Node (flashing LED) to grant
control.
If a Node has emergency voice control the LED will be ON steady.
Deny is achieved through a timeout, which is configurable.
Indicators, Controls, and Operation
98