p0761[0...1]
CU analog inputs wire breakage monitoring response threshold / CU WireBrkThresh
Access level: 2
Can be changed: U, T
Units group: -
Min
0.00
Description:
Sets the response threshold for the wire breakage monitoring of the analog inputs.
The unit for the parameter value depends on the set analog input type.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Dependency:
For the following analog input type, the wire breakage monitoring is active:
p0756[0...1] = 1 (unipolar voltage input monitored (+2 V ... +10 V)), unit [V]
p0756[0...1] = 3 (unipolar current input monitored (+4 mA ... +20 mA)), unit [mA]
Refer to: p0756
Note:
AI: Analog Input
When p0761 = 0, wire breakage monitoring is not carried out.
p0762[0...1]
CU analog inputs wire breakage monitoring delay time / CU wire brk t_del
Access level: 3
Can be changed: U, T
Units group: -
Min
0 [ms]
Description:
Sets the delay time for the wire breakage monitoring of the analog inputs.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
AI: Analog Input
p0771[0...1]
CI: CU analog outputs signal source / CU AO S_src
Access level: 2
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the analog outputs.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note:
AO: Analog Output
T: Terminal
r0772[0...1]
CU analog outputs, output value currently referred / CU AO outp_val
Access level: 3
Can be changed: -
Units group: -
Min
- [%]
Description:
Displays the actual referred output value of the analog outputs.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note:
AO: Analog Output
T: Terminal
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
20.00
Calculated: -
Scaling: -
Unit selection: -
Max
1000 [ms]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
- [%]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: -
Factory setting
2.00
Data type: Unsigned16
Data set: -
Factory setting
100 [ms]
Data type: U32 / FloatingPoint32
Data set: -
Factory setting
[0] 21[0]
[1] 27[0]
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
1-99