Siemens CU240B-2 Parameter Manual page 710

Table of Contents

Advertisement

Faults and Alarms
List of Faults and Alarms
A08757
CAN: Set COB-ID invalid
Reaction:
NONE
Acknowledge:
NONE
Cause:
For online operation, the appropriate COB-ID must be set invalid before mapping.
Example:
Mapping for RPDO 1 should be changed (p8710[0]).
--> set p8700[0] = C00006E0 hex (invalid COB-ID)
--> set p8710[0] as required.
--> p8700[0] enter a valid COB-ID
Remedy:
Set the COB-ID to invalid.
A08759
CAN: PDO COB-ID already available
Reaction:
NONE
Acknowledge:
NONE
Cause:
An existing PDO COB-ID was allocated.
Remedy:
Select another PDO COB-ID.
F30001
Power unit: Overcurrent
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has detected an overcurrent condition.
- closed-loop control is incorrectly parameterized.
- motor has a short-circuit or fault to ground (frame).
- U/f operation: Up ramp set too low.
- U/f operation: rated current of motor much greater than that of power unit.
- High discharge and post-charging current for line supply voltage interruptions.
- High post-charging currents for overload when motoring and DC link voltage dip.
- Short-circuit currents at power-on due to the missing line reactor.
- power cables are not correctly connected.
- power cables exceed the maximum permissible length.
- power unit defective.
- line phase interrupted.
Fault value (r0949, interpret bitwise binary):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
Bit 3: Overcurrent in the DC link.
Note:
Fault value = 0 means that the phase with overcurrent is not recognized.
Remedy:
- check the motor data - if required, carry out commissioning.
- check the motor circuit configuration (star-delta)
- U/f operation: Increase up ramp.
- U/f operation: Check assignment of rated currents of motor and power unit.
- check the line supply quality.
- Reduce motor load.
- Correct connection of line reactor.
- check the power cable connections.
- check the power cables for short-circuit or ground fault.
- check the length of the power cables.
- replace power unit.
- check the line supply phases.
3-710
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents