p2148[0...n]
BI: RFG active / RFG active
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the signal "ramp-function generator active" for the following signals/messages:
"Speed setpoint - actual value deviation within tolerance t_on" (BO: r2199.4)
"Ramp-up/ramp-down completed" (BO: r2199.5)
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The binector input is automatically interconnected to r1199.2 as a default setting.
p2149[0...n]
Monitoring configuration / Monit config
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the configuration for messages and monitoring functions.
Bit field:
Bit
Signal name
00
Enable alarm A07903
01
Load monitoring only in the 1st quadrant
03
n_act > p2155 own hysteresis
Dependency:
Refer to: r2197
Refer to: A07903
Note:
Re bit 00:
Alarm A07903 is output when the bit is set with r2197.7 = 0 (n_set <> n_act).
Re bit 01:
When the bit is set, load monitoring is only carried out in the 1st quadrant as a result of the positive characteristic
parameters (p2182 ... p2190).
Re bit 03:
When the bit is set, r2197 bit 1 and bit 2 are determined via separate hystereses.
p2150[0...n]
Hysteresis speed 3 / n_hysteresis 3
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency:
Refer to: p2161, r2197, r2199
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
300.00 [rpm]
Parameters
List of Parameters
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: Unsigned16
Data set: DDS, p0180
Factory setting
1001 bin
0 signal
No
No
No
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
2.00 [rpm]
FP
8010
8013