Siemens CU240B-2 Parameter Manual page 21

Table of Contents

Advertisement

p0015
Macro drive unit / Macro drv unit
CU240B-2 DP
Access level: 1
CU240E-2 DP
Can be changed: C, C(1)
CU240E-2 DP F
Units group: -
Min
0
Description:
Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0015 = 6 --> the macro file PM000006.ACX is run.
Dependency:
Refer to: p0700, p1000, p1500, r8570
Caution:
When executing a specific macro, the corresponding programmed settings are made and become active.
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
The macros in the specified directory are displayed in r8570. r8570 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
The parameter is not influenced by setting the factory setting.
r0018
Control Unit Firmware-Version / CU FW version
Access level: 3
Can be changed: -
Units group: -
Min
0
Description:
Displays the firmware version of the Control Unit.
Dependency:
Refer to: r0197, r0198
Note:
Example:
The value 1010100 should be interpreted as V01.01.01.00.
r0020
Speed setpoint smoothed / n_set smth
Access level: 2
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Displays the currently smoothed speed setpoint at the input of the speed controller or U/f characteristic (after the
interpolator).
Dependency:
Refer to: r0060
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed setpoint is available smoothed (r0020) and unsmoothed (r0060).
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
999999
Calculated: -
Scaling: -
Unit selection: -
Max
4294967295
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Parameters
List of Parameters
Data type: Unsigned32
Data set: -
Factory setting
7
Data type: Unsigned32
Data set: -
Factory setting
-
Data type: FloatingPoint32
Data set: -
Factory setting
- [rpm]
1-21