Faults and Alarms
List of Faults and Alarms
F06922
Braking resistor phase failure
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Phase failure of a braking resistor detected.
Fault values:
11 = phase U
12 = phase V
13 = phase W
See also: p3235 (Phase failure signal motor monitoring time)
Remedy:
Check the feeder cables to the braking resistors.
F07011
Drive: Motor overtemperature
Reaction:
OFF2 (NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
KTY:
The motor temperature has exceeded the fault threshold (p0605) or the timer (p0606) after the alarm threshold was
exceeded (p0604) has expired. The response parameterized in p0610 becomes active. The alarm is withdrawn if the
response threshold for wire breakage or sensor not connected is exceeded (R > 2120 Ohm).
PTC or bimetallic NC contact:
The response threshold of 1650 Ohm was exceeded or the NC contact opened and the timer (p0606) has expired.
The response parameterized in p0610 becomes active.
Possible causes:
- Motor is overloaded
- motor ambient temperature too high.
- Wire break or sensor not connected
Fault value (r0949, decimal interpretation):
200: The I2t motor model signals an overtemperature (p0612.0 = 1, p0611 > 0).
See also: p0604 (Motor temperature alarm threshold), p0605 (Motor temperature fault threshold), p0606 (Motor
temperature timer), p0610 (Motor overtemperature response)
Remedy:
- Reduce the motor load.
- check the ambient temperature and the motor ventilation.
- check the wiring and the connection of the PTC or bimetallic NC contact.
See also: p0604 (Motor temperature alarm threshold), p0605 (Motor temperature fault threshold), p0606 (Motor
temperature timer)
A07012 (N)
Drive: I2t motor model overtemperature
Reaction:
NONE
Acknowledge:
NONE
Cause:
The thermal I2t motor model (for synchronous motors) identified that the temperature alarm threshold was exceeded.
See also: r0034 (Motor utilization), p0605 (Motor temperature fault threshold), p0611 (I2t motor model thermal time
constant)
Remedy:
- check the motor load and if required, reduce.
- check the motor ambient temperature.
- check the thermal time constant p0611.
- check the overtemperature fault threshold p0605 (= alarm threshold for the I2t motor model, see p0612)
A07015
Drive: Motor temperature sensor alarm
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error was detected when evaluating the temperature sensor set in p0601.
With the fault, the time in p0607 is started. If the fault is still present after this time has expired, then fault F07016 is
output; however, at the earliest, 50 ms after alarm A07015.
Possible causes:
- wire breakage or sensor not connected (KTY: R > 2120 Ohm).
- measured resistance too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm).
Remedy:
- make sure that the sensor is connected correctly.
- check the parameterization (p0601).
See also: r0035 (Motor temperature), p0601 (Motor temperature sensor type), p0607 (Temperature sensor fault
timer)
3-690
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
© Siemens AG 2011 All Rights Reserved