List of Faults and Alarms
F01250
CU: CU-EEPROM incorrect read-only data
Reaction:
NONE (OFF2)
Acknowledge:
POWER ON
Cause:
Error when reading the read-only data of the EEPROM in the Control Unit.
Fault value (r0949, decimal interpretation):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON.
- replace the Control Unit.
A01251
CU: CU-EEPROM incorrect read-write data
Reaction:
NONE
Acknowledge:
NONE
Cause:
Error when reading the read-write data of the EEPROM in the Control Unit.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
For alarm value r2124 < 256, the following applies:
- carry out a POWER ON.
- replace the Control Unit.
For alarm value r2124 >= 256, the following applies:
- clear the fault memory (p0952 = 0).
- replace the Control Unit.
F01505 (A)
BICO: Interconnection cannot be established
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A PROFIdrive telegram has been set (p0922).
An interconnection contained in the telegram was not able to be established.
Fault value (r0949, decimal interpretation):
Parameter receiver that should be changed.
Remedy:
Establish another interconnection.
F01510
BICO: Signal source is not float type
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested connector output does not have the correct data type. This interconnection is not established.
Fault value (r0949, decimal interpretation):
Parameter number to which an interconnection should be made (connector output).
Remedy:
Interconnect this connector input with a connector output having a float data type.
F01511 (A)
BICO: Interconnection with different scalings
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested BICO interconnection was established. However, a conversion is made between the BICO output and
BICO input using the reference values.
- the BICO output has different normalized units than the BICO input.
- message only for interconnections within a drive object.
Example:
The BICO output has, as normalized unit, voltage and the BICO input has current.
This means that the factor p2002/p2001 is calculated between the BICO output and the BICO input.
p2002: contains the reference value for current
p2001: contains the reference value for voltage
Fault value (r0949, decimal interpretation):
Parameter number of the BICO input (signal sink).
Remedy:
Not necessary.
3-668
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011